Compact, AC line supply 3 x 380-500 V
According to international requirements VLT type 5352 5452 5502 5552
Normal overload current (110%):
Output current
I
VLT,N
[A] (380-440 V)
600 658 745 800
I
VLT, MAX
(60 s) [A] (380-440
V)
660 724 820 880
I
VLT,N
[A] (441-500 V)
540 590 678 730
I
VLT, MAX
(60 s) [A] (441-500
V)
594 649 746 803
Output S
VLT,N
[kVA] (400 V)
416 456 516 554
S
VLT,N
[kVA] (460 V)
430 470 540 582
S
VLT,N
[kVA] (500 V)
468 511 587 632
Typical shaft output
[kW] (400 V) 315 355 400 450
[HP] (460 V) 450 500 550/600 600
[kW] (500 V) 355 400 500 530
High overload torque (160 %):
Output current
I
VLT,N
[A] (380-440 V)
480 600 658 695
I
VLT, MAX
(60 s) [A] (380-440
V)
720 900 987 1042
I
VLT,N
[A] (441-500 V)
443 540 590 678
I
VLT, MAX
(60 s) [A] (441-500
V)
665 810 885 1017
Output S
VLT,N
[kVA] (400 V)
333 416 456 482
S
VLT,N
[kVA] (460 V)
353 430 470 540
S
VLT,N
[kVA] (500 V)
384 468 511 587
Typical shaft output
[kW] (400 V) 250 315 355 400
[HP] (460 V) 350 450 500 550
[kW] (500 V) 315 355 400 500
Max. cable cross-section
to motor and load sharing
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. cable cross-section
to brake
[mm
2
]
4,6
[AWG]
2,4,6
2x185
2x350 mcm
Normal overload current (110%):
Rated input current
I
L,N
[A] (380-440 V)
590 647 733 787
I
L,N
[A] (441-500 V)
531 580 667 718
High overload torque (160 %):
Rated input current
I
L,N
[A] (380-440 V)
472 590 647 684
I
L,N
[A] (441-500 V)
436 531 580 667
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. pre-fuses (line) [-]/
UL
[A]
1
700/700 900/900 900/900 900/900
Efficiency
3
0,98
Power loss
Normal overload [W]
7630 7701 8879 9428
High overload [W] 6005 6960 7691 7964
Weight
IP 00 [kg]
221 234 236 277
Weight
IP 21/NEMA 1 [kg]
263 270 272 313
Weight
IP 54/NEMA 12 [kg] 263 270 272 313
Enclosure IP 00, IP 21/NEMA 1 and IP 54/NEMA 12
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with
national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply, motor and load sharing: M10 (compression lug), 2xM8 (box lug), M8 (brake)
VLT
®
5000 Series
22 MG.51.C5.22 - VLT