Electrical data
Bookstyle and Compact, Mains supply 3 x 200 -
240 V
According to international requirements VLT type 5001 5002 5003 5004 5005 5006
Output current
I
VLT,N
[A]
3.7 5.4 7.8 10.6 12.5 15.2
I
VLT, MAX
(60 s) [A]
5.9 8.6 12.5 17 20 24.3
Output (240 V) S
VLT,N
[kVA]
1.5 2.2 3.2 4.4 5.2 6.3
Typical shaft output
P
VLT,N
[kW]
0.75 1.1 1.5 2.2 3.0 3.7
Typical shaft output
P
VLT,N
[HP]
1 1.5 2 3 4 5
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2
)
4/10
4/10 4/10 4/10 4/10 4/10
Rated input current
(200 V)I
L,N
[A]
3.4 4.8 7.1 9.5 11.5 14.5
Max. cable
cross-section power [mm
2
]/[AWG]
2
)
4/10
4/10 4/10 4/10 4/10 4/10
Max. pre-fuses
[-]/UL
1)
[A]
16/10 16/10 16/15 25/20 25/25 35/30
Efficiency
3)
0.95 0.95 0.95 0.95 0.95 0.95
Weight IP 20 EB Bookstyle [kg] 7 7 7 9 9 9.5
Weight IP 20 EB Compact [kg] 8 8 8 10 10 10
Weight IP 54 Compact [kg] 11.5 11.5 11.5 13.5 13.5 13.5
Power loss at
max. load.
[W] 58 76 95 126 172 194
Enclosure
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 13