PNU Parameter Factory setting Range Changes 4-Setup Conversion Data
# description during operation index type
100 Configuration Speed control, open loop No Yes 0 5
101 Torque characteristics High - constant torque Yes Yes 0 5
102 Motor power Depends on the unit 0.18-600 kW No Yes 1 6
103 Motor voltage Depends on the unit 200 - 600 V No Yes 0 6
104 Motor frequency 50 Hz / 60 Hz No Yes 0 6
105 Motor current Depends on the unit 0.01-I
VLT,MAX
No Yes -2 7
106 Rated motor speed Depends on the unit 100-60000 rpm No Yes 0 6
107 Automatic motor adaptation, AMA Adaptation off No No 0 5
108 Stator resistor Depends on the unit No Yes -4 7
109 Stator reactance Depends on the unit No Yes -2 7
110 Motor magnetizing, 0 rpm 100 % 0 - 300 % Yes Yes 0 6
111 Min. frequency normal
magnetizing
1.0 Hz 0.1 - 10.0 Hz Yes Yes -1 6
112
113 Load compensation at low speed 100 % 0 - 300 % Yes Yes 0 6
114 Load compensation at high speed 100 % 0 - 300 % Yes Yes 0 6
115 Slip compensation 100 % -500 - 500 % Yes Yes 0 3
116 Slip compensation time constant 0.50 s 0.05 - 1.00 s Yes Yes -2 6
117 Resonance dampening 100 % 0 - 500 % Yes Yes 0 6
118 Resonance dampening time
constant
5ms 5-50ms Yes Yes -3 6
119 High starting torque 0.0 sec. 0.0 - 0.5 s Yes Yes -1 5
120 Start delay 0.0 sec. 0.0 - 10.0 s Yes Yes -1 5
121 Start function Coasting in start delay time Yes Yes 0 5
122 Function at stop Coasting Yes Yes 0 5
123 Min. frequency for activating
function at stop
0.0 Hz 0.0 - 10.0 Hz Yes Yes -1 5
124 DC holding current 50 % 0 - 100 % Yes Yes 0 6
125 DC braking current 50 % 0 - 100 % Yes Yes 0 6
126 DC braking time 10.0 sec. 0.0 - 60.0 sec. Yes Yes -1 6
127 DC brake cut-in frequency Off 0.0-par. 202 Yes Yes -1 6
128 Motor thermal protection No protection Yes Yes 0 5
129 External motor fan No Yes Yes 0 5
130 Start frequency 0.0 Hz 0.0-10.0 Hz Yes Yes -1 5
131 Initial voltage 0.0 V 0.0-par. 103 Yes Yes -1 6
145 Minimum DC brake time 0 sec. 0 - 10 sec. Yes Yes -1 6
MG.51.A9.02 - VLT is a registered Danfoss trademark
179

Table of Contents

Other manuals for Danfoss VLT 5027

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5027 and is the answer not in the manual?

Danfoss VLT 5027 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5027
CategoryDC Drives
LanguageEnglish

Related product manuals