VLT
®
5000 Series
â–  mains supply 3 x 525 - 690 V
According to international requirements VLT type 5122 5152 5202 5252 5302 5352
Normal overload torque (110 %):
Output current I
VLT,N
[A] (525-550 V) 162 201 253 303 360 418
I
VLT, MAX
(60 s) [A]
(525-550 V)
178 221 278 333 396 460
I
VLT,N
[A] (551-690 V) 155 192 242 290 344 400
I
VLT, MAX
(60 s) [A]
(551-690 V)
171 211 266 319 378 440
Output S
VLT,N
[kVA] (550 V) 154 191 241 289 343 398
S
VLT,N
[kVA] (575 V) 154 191 241 289 343 398
S
VLT,N
[kVA] (690 V) 185 229 289 347 411 478
Typical shaft output [kW] (550 V) 110 132 160 200 250 315
[HP] (575 V) 150 200 250 300 350 400
[kW] (690 V) 132 160 200 250 315 400
High overload torque (160 %):
Output current I
VLT,N
[A] (525-550 V) 137 162 201 253 303 360
I
VLT, MAX
(60 s) [A]
(525-550 V)
206 243 302 380 455 540
I
VLT,N
[A] (551-690 V) 131 155 192 242 290 344
I
VLT, MAX
(60 s) [A]
(551-690 V)
197 233 288 363 435 516
Output S
VLT,N
[kVA] (550 V) 131 154 191 241 289 343
S
VLT,N
[kVA] (575 V) 130 154 191 241 289 343
S
VLT,N
[kVA] (690 V) 157 185 229 289 347 411
Typical shaft output [kW] (550 V) 90 110 132 160 200 250
[HP] (575 V) 125 150 200 250 300 350
[kW] (690 V) 110 132 160 200 250 315
Max. cable
cross-section to motor
[mm
2
]
4,6
[AWG]
2,4,6
2x70
2x2/0
2 x 185
2 x 350 mcm
Max. cable
cross-section to
loadsharing and brake
[mm
2
]
4,6
[AWG]
2,4,6
2x70
2x2/0
2 x 185
2 x 350 mcm
Normal overload torque (110 %):
Rated input current I
L,N
[A] (550 V) 158 198 245 299 355 408
I
L,N
[A] (575 V) 151 189 234 286 339 390
I
L,N
[A] (690 V) 155 197 240 296 352 400
High overload torque (160 %):
Rated input current I
L,N
[A] (550 V) 130 158 198 245 299 355
I
L,N
[A] (575 V) 124 151 189 234 286 339
I
L,N
[A] (690 V) 128 155 197 240 296 352
Max. cable
cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
2x70
2x2/0
2 x 185
2 x 350 mcm
Max. pre-fuses (mains)
[-]/UL
[A]
1
315 350 350 400 500 550
Efficiency
3
0,98
Power loss Normal overload [W] 3114 3612 4292 5155 5821 6149
High overload [W] 2664 2952 3451 4275 4875 5185
Weight IP 00 [kg] 82 91 112 123 138 151
Weight IP 21/Nema1 [kg] 96 104 125 136 151 165
Weight IP 54/Nema12 [kg] 96 104 125 136 151 165
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminal
s.
Always comply with national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply and motor: M10; Brake and loadsharing: M8
MG.51.A9.02 - VLT is a registered Danfoss trademark
32

Table of Contents

Other manuals for Danfoss VLT 5027

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5027 and is the answer not in the manual?

Danfoss VLT 5027 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5027
CategoryDC Drives
LanguageEnglish

Related product manuals