VLT® Automation Drive FC302
no yes
Par. 1-00 Configuration Mode
Par. 1-00 Configuration Mode
<<Speed Closed Loop>> [1]
Par. 1-01 Motor Control Principle
Par. 1-01 Motor Control Principle
<<Flux with motor feedback>> [3]
Par. 1-02 Flux Motor Feedback Source
<<24V encoder [1] or MCB102 [2]>>
Par. 1-03 Torque Characteristics
Par. 1-06 Clockwise Direction
no yes
no yes
Start with factory setting value and increase it if
the start behaviour is not good enough
Start with a value around 1s and reduce it
afterwards
Make sure that the hoisting direction is in
clockwise motor direction
<<Hoist Mech Brake Rel.>> [6]
Minimum slip speed
Premag is prefered but not always possible
Minimum slip speed
yes
Cone rotor
no yes
Par. 2-21 Activate Brake Speed
Par. 2-23 Activate Brake Delay
Par. 2-25 Brake Release Time
Motor Thermal
Protection
Brake Resistor
settings
Par. 2-21 Activate Brake Speed
[100…150rpm]
Par. 2-23 Activate Brake Delay
[0,2…0,5s]
Par. 2-15 Brake Check <<Trip>> [2]
Par. 2-18 Brake Check Condition <<At
Power Up>> [0]
Speed Closed Loop
<<VVC+/Flux Clockwise>> [5]
[100…400rpm]
[nominal motor current A]
<<Active Load>> [1]
Par. 1-90 Motor Thermal Protection
<<Thermistor Trip>>[2]
Par. 1-91 Motor External Fan
if available [1]
Par. 1-93 Thermistor Resource
Analog Input 53 [1] or
Analog Input 54 [2]
Par. 2-11 Brake Resistor [Ohm]
Par. 2-12 Brake Power Limit [kW]
Par. 2-13 Brake Power Monitor
<<Trip>> [2]
Cone rotor
Motor Settings
Par. 1-50 Motor Magnetization At Zero
Speed <<[110-130%]>>
Par. 1-53 Model Shift Frequency
[8-10Hz]
Par. 1-66 Min Current At Low Speed
[100-150%]
Par. 1-47 Torque Calibration
<<1st start after pwr-up>> [1]
Start - Stop Adjustments
<<Hoist Mech Brake Rel.>> [6]
Par. 1-80 Function At Stop
<<Coast or Premag>> [0 or 3]
Par. 1-81 Min Speed for Function At
Stop [>5rpm… nslip]
General Settings
Par. 1-20 Motor Power [kW]
Start
Speed feedback
Recommended Drive settings for hoist applications with drive sw version 7.29 and higher
Par. 1-22 Motor Voltage [V]
Par. 1-23 Motor Frequency [Hz]
Par. 1-24 Motor Nominal Current [A]
Par. 1-25 Motor Nominal Speed [rpm]
Par. 1-29 Automatic Motor Adaptation
[1]
Speed feedback
Par. 1-80 Function At Stop
<<Coast>> [0]
Par. 1-81 Min Speed for Function At
Stop [100…500rpm]
Par. 1-53 Model Shift Frequency
[8-10Hz]
Par. 1-66 Min Current At Low Speed
[120-150%]
<<Active Load>> [1]
[0,1…0,5s]
Page 1 of 3