NOTE:
The lamp work by 1 minute.
-Power supply accessories (terminals 12V DC and COMMON): connect to
feed with direc tcurrent 12Vtophotocell.
- Open / Close button: connect12V and Open / Close, as desired.
-Safety devices: connect the signal of return of the device to the board
betweenthe terminal of COMMON and IN.
-Lamp: to connect a lamp it must be connected to the L-LAMP terminals
DIP SET UP
1 LIMIT SWITCHES /DEAD MAN
ON work normal, the switch limits are in the motor.
OFF Limit switches (at Common, Opening and Closing
terminals).
2 DEAD MAN IN OPENING MANEUVER (DIP 1 ON)
ON To start opening maneuver, is necessary to hold pressed
the transmitter’s button or the PROG switch. If the button is
not held, maneuver will stop.
OFF Opening is set as direct order operation.
3 DEAD MAN IN CLOSING MANEUVER (DIP1 ON)
ON To start the closing maneuver, hold pressed the
transmitter’s button or the PROG button. If the button is not
held, maneuver will stop.
OFF Closing is set as direct order operation.
4 PHOTOBEAM
ON Photocell is disabled (It is not necessary to
bridge the security input). Automatic closure is not available
with this position.