Supply Voltage: 85 - 300VAC (L1-N)
50 - 60Hz nominal (± %10) (L1-N)
Generator Input: 70 - 300 V AC (P-N)
Measurement Inputs:
Voltage: 10 - 300 V AC (Ph-N)
20 - 520 V AC (Ph-Ph)
Current: 0.05 - 5.50 A AC
Frequency: 30 - 100 Hz
Accuracy:
Voltage: % 0.5 + 1 digit
Current: % 0.5 + 1 digit
Frequency: % 0.5 + 1 digit
Power(kW,kVAr): %1.0 + 2 digit
Cos: %0.5 + 1 digit
Measurement Range:
CT Range: 5/5A to 5000/5A
VT Range: 0.1/1 to 200.0/1
kW Range: 0.1 kW to 6.5MW
Power Consumption: < 10 VA
Loading:
Voltage Inputs: < 0.1VA per phase
Current Inputs: < 0.5VA per phase
Number of Steps: 12-15
Relay Outputs: 5A @ 250V A
Serial Port:
Signal Type: RS-485
Communication: Modbus RTU
Baud Rate: 2400-115200 selectable
Isolation: 500V AC, 1 minute
Operating Temperature: -20°C to +70 °C (-4 to +158 °F)
Maximum Humidity: %95 non-condensing.
Degree of Protection:
IP 54 (Front Panel)
IP 30 (Rear Panell)
Enclosure:
Non-flammable,
ROHS compliant,
Flame retardant,
High temp. ABS/PC
UL94-V0
Installation: Flush mounting with rear brackets.
Dimensions: 164x164x69mm (WxHxD)
Panel Cutout: 140x140 mm
Weight: 450 gr (approx.)
2006/95/EC (LVD)
2004/108/EC (EMC)
TS-EN 61010 (safety)
TS-EN 61326 (EMC)