OWNER’S MANUAL
ELECTRICAL CONNECTIONS
The DCA unit is factory pre-wired. Field wiring is limited
to power wire and the installation of wiring for 24V
controls.
Provide and install a main disconnect switch within
close vicinity of the dehumidifier. Refer to the unit
nameplate or electrical information (Following Chart) for
proper voltage, minimum ampacity and maximum main fuse
protection. All wiring and main disconnect switch should
be provided in accordance with all local, state and national
electric codes (N.E.C.).
IMPORTANT
Make sure the DCA unit is properly grounded with
correct gauge of wire via the ground lug terminal located in
the control panel. Failure to properly ground unit will void
all warranties. Supply voltage must not vary more than 10%
of the nameplate voltage while the unit is operating.
Chart A
Fuse & Ampacity Rating
The control wiring should be done according to the
wiring diagram provided with the unit. The DCA control
circuit operates at 24V.
CONTROLS, LOCATION & MOUNTING
Locate controls in an area of natural room air
circulation usually near the return air inlet. Avoid areas of
hot spots from warm air ducts, radiators or exposure to
sunlight or direct room lighting. Avoid mounting controls on
cold outside masonry walls, near door, windows or air
conditioning outlets.
Do not locate controls in a room that is not being
conditioned by the dehumidification system, unless system
has remote sensors (optional).
Controls should be mounted 5 feet from floor level on an
interior wall. All controls must be level.
MAXIMUM MINIMUM
MODEL VOLTS PHASE FUSE SIZE AMPACITY
DCA500 208/2301 25 amp 19.2
DCA900/ 208/230 1 30 amp 22.8
900WH 208/230 3 20 amp 14.2
460V 3 10 amp 7.0
DCA1400/ 208/230 1 40 amp 30.8
1400WH 208/230 3 25 amp 19.3
460V 3 12 amp 9.6
DCA2000/ 208/230 1 50 amp 35.6
2000WH 208/230 3 35 amp 25.6
460V 3 17.5 amp 12.4
DCA2500/ 208/230 1 70 amp 48.9
2500WH 208/230 3 40 amp 30.6
460V 3 20 amp 14.6
DCA3000/ 208/230 1 60 amp 43.6
3000WH 208/230 3 45 amp 32.4
460V 3 20 amp 15.8
DCA3300/ 208/230 3 60 amp 41.7
3300WH 208/230 3 30 amp 21.8
DCA3500/ 208/230 1 90 amp 70.9
3500WH 460V
DCA3800/ 208/230 3 70 amp 50.6
3800WH 460V 3 35 amp 25.8
DCA4000/ 208/230 1 100 amp 90.5
4000WH 460V
DCA4200/ 208/230 3 80 amp 58.6
4200WH 460V 3 40 amp 28.8
DCA5400/ 208/230 3 100 amp 73.8
5400WH 460V 3 50 amp 38.8
DCA7000 208/230 3 120 amp 83.9
7000WH 460V 3 60 amp 41.5
DCA8000 208/230 3 110 amp 92.4
8000WH 460V 3 60 amp 47.1
DCA9000/ 208/230 3 125 amp 108.5
9000WH 460V 3 70 amp 53.4
DCA11000 208/230 3 175 amp 154.0
460V 3 90 amp 77.5
575V 3 70 amp 62.7
DCA14000 208/230 3 250 amp 207.3
460V 3 125 amp 102.4
575V 3 110 amp 89.7
Floor
Approx
5 Feet
Thermostat
or Temperature Sensor
Humidistat
or Humidity Sensor
Standard 18ga. or 20ga. low voltage 24 volt wiring is required
for the controls of the dehumidifier.