DRAIN PUMP REMOVAL INSTRUCTIONS
Additional issues to be inspected by the installer upon service replacement:
1
The drain pump must be level.
2
No pinched water lines.
3
No interference with electrical cords or wiring.
4
The drain pump should not set on any obstacles, wiring, etc.
5
Secure all hose clamps leading to and from the drain pump.
6
Insure that the vent tube height is adequate — 18” (457mm) minimum.
7
Insure that drain height is adequate — maximum of 8ft (2.4m).
8
Insure that drain length is adequate — maximum of 20ft (6.1m).
9
Checked for water leaks after installation of the drain pump.
!0
Check for vibrations caused by improper installation.
!1
Insure that there is no interference with back access cover.
!2
Insure that the hole grommets are in place at each location so that any vent or drain
tubes do not rub on any sharp surfaces.