124 RR
R
Operating instructions and warnings
22
P019
Time of automatic closing (expressed in sec). If = 0 the automatic closing is deactivated
0 10 .............................................. 255
P020
Time of pre-flashing (expressed in sec)
0..... 2 .............................................. 15
P021
Unused parameter
P022
Unused parameter
P023
Collectivity function: if it is activated it deactivates both start and pedestrian inputs for
the whole duration of automatic opening and closing
000
deactivated
001
activated
P024
Ram blow function: if it is activated, it pushes the motors closed for one second before
each opening movement, so as to ease motor’s start
000
deactivated
001
activated
P025
Operating program: reversal (start->open, start->close, start->open ...), step-by-
step (start->open, start->stop, start-close...)
000
reversal
001
step-by-step
P026
Photocell function even while opening: if it is activated, the photocell stops the movement
while opening until the obstacle is removed. In any case it reverses the direction of
movement while closing
000
Photocell activated only in closing
001
Photocell activated also in opening
P027
Clean contact operation :
- If = 0, open gate warning light, the contact is always closed when the gate is opened,
it opens again only when the closing movement is completed
- If different from 0, courtesy light, the contact is closed during every movement, it opens
again when the motor stops according to a pre-settable delay (expressed in sec)
0.................................................... 255
P028
Short reversal at end of stroke: when the door/gate reaches the end of stroke, it reverses
shortly the movement so as to “release” the mechanical stress due to the door/gate
pressure on the end of stroke itself.
000
deactivated
001
activated
P029
Unused parameter
P030
“PED” input functioning
-If = 0 it ensures the door/gate closing in any situation. The input opens and works normally
-If = 1 the “PED” input starts the closing, the “AP” input starts the opening
-If >1 The selected value indicates the duration of the pedestrian stroke (expressed as
a % of the total stroke)
000
centralized closing
001
separate closing
>001
pedestrian
P031
Ramp rate duration
-If =0 the motor starts immediately at the selected speed
-If =1 the motor speeds up progressively until it reaches the selected speed
000
fast ramp
001
slow ramp
P032
Reaction at detection of an obstacle while opening
- If=0 the door inverses travelling direction
- If different from 0 the door inverses travelling direction only for the set time (expressed in sec)
0...................................................... 10
P033
Reaction at detection of an obstacle while closing
-If=0 the door inverses travelling direction
-If (0 the door inverses travelling direction only for the time set (expressed in sec)
0...................................................... 10
P034
Unused parameter
1
The default value, set by manufacturer at the factory, is written in bold and underlined.
2
Column reserved to the installer to fill in with the automation personalised parameters Table 2 Parametres
3
Inactive channel.