124 RR
Operating instructions and warnings
15
Table 1 Terminal board connection
8 USE INSTRUCTIONS
Press on the “OK” key to check if all inputs have been properly connected.
F
C
A
PE
D
ST
A
RT
FCC
FOT
O
ST
O
P
SIC
1-2 24 V a.c. 24 V a.c. transformer power supply input
3-4
24 V Batt 24 V d.c. battery power supply input (Follow carefully polarity indications)
5-6
LC/SCA
Free contact max. capacity 5 A : this contact can be used to control an open gate
warning light (P27=0) or a courtesy lamp (P27≠0)
7-8
LAMP
Flashing light output 24 V d.c. max 15W art. Lumy 24S The intermittent output does not
demand the use of a flashing light card.
9
COM Common safety devices
9-10
+24VAUX
+24 V d.c. power supply output for controlled safety devices. To be used as power
supply of photocell transmitters (in all cases) and of safety devices when testing these
latter before each operation
9-11
+24VSIC
+24 V d.c. power supply output for auxiliary circuits and uncontrolled safety devices To
be used as power supply of any auxiliary devices, photocell receivers (in all cases), and
of safety devices when testing these latter before each operation
12-13
Motor output 24 V d.c. max 70W
14
FCA N.C. input limit switch while opening. If unused, short circuit to terminal n° 21
15
FCC N.C. input limit switch while closing. If unused, short circuit to terminal n° 21
16
START N.O. open input. If activated, it opens or closes both motors. It can work in “reversal”
mode (P25=0) or “step-by-step” mode (P25=1)
17
PEDON N.O. pedestrian opening input. If activated, it opens the motor
18
STOP N.C. stop input. If activated, it stops the movement of both motors during any opera-
tion. If unused, short circuit to terminal n° 21
19
FOTOC
N.C. Photocell input. In case of activation it reverses the movement only while closing
(P26=0) or it reverses the movement while closing and stops while opening (P26=1).
If unused, short circuit to the terminal n°21
20
SIC
N.C. leaf safety device input. In case of activation it reverses the movement (P18=0) or
it stops it (P18=1). If unused, short circuit to the terminal n°21
21
COM Common inputs
22
Aerial ground input
23
Aerial signal input
M
After making all connections to the terminal board, remember to short-circuit, whenever needed, any
unused input (see “connection to the control board”) and power the card: on the display you will read for
a few seconds “rES-” followed by the symbol “----” which stands for gate closed.
8.1 Visualisation of inputs status