EasyManuals Logo

Dectron LD Series Installation Manual

Default Icon
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
H – Electric Connection
INM.XX.X.00 H-5 April, 2018
BACnet MSTP communication is established over RS-485 serial port:
Connect two wires to pins 5 and 6 on J8 terminal (see Pic. H.3):
o use twisted-pair wires only;
o If both, ROP and BACnet MSTP, connection is required – connect BACnet MSTP on terminal J8 as
described above and relocate ROP connection – contact the factory for guidance.
Certain configuration of dehumidifier control software, BACnet-based BMS and local network settings may be
required to establish proper communication, access desired parameters/points, etc.– refer to BACnet Objects and
BACnet PICS documents and other related documents; contact the factory as needed.
Modbus
Modbus communication is established same way as BACnet MSTP (over RS-485 serial port). Follow the same
recommendation for connection as for BACnet MSTP – see above.
Certain configuration of dehumidifier control software, Modbus-based BMS and local network settings may be
required to establish proper communication, access desired parameters/points etc.– refer to Modbus Registers
document and other related documents; contact the factory as needed.
LON
LON communication is established over RS-232 serial port (hosted on the control board terminal JCOM – see Pic.
H.3), and requires LonWorks Gateway (installed at the factory, if initially requested, or field-installed).
Pic. H.5 and Table H.2 below show standard connections layout for dehumidifier control board terminal JCOM and
LonWorks Gateway.
Certain configuration of dehumidifier control software, LON-based BMS and local network settings may be
required to establish proper communication, access desired parameters/points, etc.– refer to LON Objects
document and other related documents; contact the factory as needed.
LonWorks Gateway must be pre-programmed and pre-configured (if field-installed) – refer to respective
device manual for configuration and troubleshooting (indicators pattern, etc.)
Table H.2
Gateway pin JCOM pin Function
Power connector
1 5 24VDC power (24+)
2 4 24VDC common (DCC)
RS232/422/485 connector
2 3 Serial port 232 (RX)
3 2 Serial port 232 (TX)
5 10 24VDC common (DCC)
Pic.H.5

Table of Contents

Other manuals for Dectron LD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron LD Series and is the answer not in the manual?

Dectron LD Series Specifications

General IconGeneral
BrandDectron
ModelLD Series
CategoryDehumidifier
LanguageEnglish

Related product manuals