Parameter 59: Opening pressure
Range : 35 - 100
Default : 100
Units : %
Function
Pressure setting during the opening phase.
Description
You can adjust the pressure during the opening movement of the beam. This value is a
percentage of the maximum pressure (machine parameter 25).
Note
Make sure that the value for this parameter is high enough! If it is too low the beam will not
move. This is a dangerous situation! When after switching on the pump the beam does not move
upwards, the control sets the output signal UDP active.
When the beam is below its reference point it will come down without finding its reference when
a closing command is given. This can damage the tools!
Therefore the minimum value is set to 35%.