Room Temperature Sensor RTS-20xxx (Rev 3.0) Installation & Application Guide
Page 6 of 13 Document Edition 2.3
Wiring Diagram
The following wiring diagram displays a controller with 3 separate inputs from the sensor:
Temperature, Setpoint and Override. In this instance the jumper on the RTS-20JPS should
be set to the middle Override position. The controller in this instance has the Temperature
connected to Input 1, the Setpoint connected to Input 2 and the Override signal connected
to Input 3. If the controller requires separate Ground connections for each input, connect
the Common from the RTS-20JPS to each Input ground terminal. The labeling on the
backplate of the RTS-20JPS is labeled: TMP for the 10k Thermistor, SET for the 20k
Setpoint adjust potentiometer and OVR for the Override input.
4-20mA 10k 5V 10V
4-20mA 10k 5V 10V
4-20mA 10k 5V 10V
4-20mA 10k 5V 10V
4-20mA 10k 5V 10V
4-20mA 10k 5V 10V
IP1
GND
IP2
GND
IP3
GND
IP4
GND
IP5
GND
IP6
GND
321
12 PIN
4 5 876 9 10 11 12
CONTROLLER
24~ GND
PWR
+-
NET
OVR SET COM TMP
`
24 VAC Power
Connection for optional
Service Port with RTS-
20Jxx
Network Connection
for optional Service
Port with RTS-20Jxx
BACKPLATE
Optional Push-button
and Setpoint
Adjustment Input
Connection
24~ GND
+
PWR
NET
-
OVR SET COM TMP
Room Temperture