Chapter 13 IO-Link Communication Module AS04SIL
13-41
13
IO-Link
Event
Codes
Type
Event Solution
Source
Warning Error
Notifica-
tion
IO-Link
Master
IO-Link
Device
16#8CA8
V
Device power supply
voltage under-run L+
(<9V)
Check the external power
supply
V
16#8CA9
V
Illegal device ID
Check device
specifications
V
16#8CAA
V
HWCONFIG configured
process data exceeding
the IO-Link process
data range
Check device
specifications
V
16#8CAB
V
IO-Link process data
exceeding HWCONFIG
configured process
data range
Scan the device and
download the configuration
again
V
16#8CAC
V
Data storage error
Contact the factory
V
0xFF21
V
New connected device
V
0xFF22
V
Device disconnected
Check installation
V
0xFF23
V
Data storage
identification mismatch
Set the Data Storage
access locked and set it to
backup / restore and then
backing up data according
to actual placement.
V
0xFF24
V
Data storage not
sufficient
Check device
specifications
V
0xFF25
V
Data storage parameter
access denied
Check device
specifications
V

Table of Contents