AS Series Module Manual
7- 28
_7
CR#
Operand Function Description Defaults
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
601
631
661
691
721
751 781 811
SV SV Target value 0
602
632
662
692
722
752 782
812
PID_MODE
PID control
mode
0: automatic
control
When PID_MAN
is switched from
1 to 0, the
output value
(MV) is included
in the automatic
algorithm.
1: the parameters
are tuned
automatically for
the temperature
control. When
the tuning is
complete, the
device is
automatically
reset to 0, and
the parameters
Kc_Kp, Ti_K
i
,
Td_K
d
, and Tf
are set
appropriately.
0
603
633
663
693
723
753 783
813
PID_MAN
PID A/M
mode
0: auto; the MV is
output based
on the PID
algorithm.
1: manual; the MV
is output based
on the MOUT.
When
0