Chapter 7 Temperature Measurement Module AS04/08TC
7- 31
7_
CR#
Operand Function Description Defaults
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
PV).
616
646
676 706 736
766
796
826
PID_DIR
PID forward/
reverse
direction
0: heating action
(E=SV-PV)
1: cooling action
(E=PV-SV)
0
617
647
677 707 737
767
797
827
ERR_DBW
Range within
which the
error value is
counted as 0
The error value (E)
is the difference
between the SV
and the PV. When
this setting is 0,
the function is not
enabled. When
this setting is
enabled, the CPU
module checks
whether the
present difference
is less than the
absolute value of
ERR_DBW, and it
checks whether
the present
difference meets
the cross status
condition. If the
present difference
is less than the
absolute value of
ERR_DBW and it
meets the cross
status condition,
the present error is
counted as 0, and
the PID algorithm
0