EasyManua.ls Logo

Delta AS04TC-A

Delta AS04TC-A
632 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AS Series Module Manual
7- 8
_7
CR# Name Description
Atr. Defaults
bit8: error in the power supply
bit9: error in the module hardware
bit10: error in calibration
bit11: error in CJC temperature
201
Instruction set
16#0101: record the peak value again for
channel 1
16#0102: record the peak value again for
channel 2
16#0104: record the peak value again for
channel 3
16#0108: record the peak value again for
channel 4
16#010F: record the peak values again for
channels 14
16#0201: enable recording for channel 1
16#0202: enable recording for channel 2
16#0204: enable recording for channel 3
16#0208: enable recording for channel 4
16#020F: enable recording for channels 1–4
16#0211: disable recording for channel 1
16#0212: disable recording for channel 2
16#0214: disable recording for channel 3
16#0218: disable recording for channel 4
16#021F: disable recording for channels 1–4
16#0502: restore default settings
W 0
210
The maximum peak
value for channel 1
Integer format; the maximum peak value for
analog inputs
R
-
211
The maximum peak
value for channel 2
-
212
The maximum peak
value for channel 3
-
213
The maximum peak
value for channel 4
-
214
The minimum peak
Integer format; the minimum peak value for
R -

Table of Contents