12
1013H 2 V V Pulse width of output 2 Range: 1 ~ 9,999; Unit: 10ms, 0: Sustained mode
1014H 0 V V Decimal position 0 ~ 3
1015H 1000 V V Pre-scale value Range: 1 ~ 99,999; Unit: 0.001
1016H 0 V Data save on loss power 0: No action; 1: Save present data
1017H 0 V V V Reset min. pulse width 0: 20ms; 1: 1ms
1018H 0 V Tachometer output mode 0: Lo-Lo; 1: Lo-Hi; 2: Hi-Lo; 3: Hi-Hi (Tachometer)
1019H 0 V Delay time while power on 0 ~ 999; Unit: 0.1s
101AH 0 V Average of input data 0 ~ 3
101BH 0 V V V Front panel lock status 0: Normal; 1: Lock all; 2: SV can be set
101EH V V V Read version Read only
Value Timer Output Mode
Timer
Display
Counter
Output
Mode
Value Timer Output Mode
Timer
Display
Counter
Output Mode
0 Signal ON Delay1 0.01s F 6 Repeat Cycle 1 min Q
1 Signal ON Delay2 0.1s N 7 Repeat Cycle Hold hr, min, 1s A
2 Signal OFF Delay 1s C 8 Repeat Cycle 2 hr, 1min S
3 Signal ON min, 0.01s R 9 Signal Cumulate 1hr T
4 Power ON Delay min, 0.1s K 10 Signal Twin ON Start D
5 Power ON Delay Hold 0.1 min P 11 Signal Twin OFF Start
Table 1
Tachometer Function
Measuring Rotation speed: Measuring pulse width and determining current frequency
Output methods: Lo-Lo, Lo-Hi, Hi-Lo, Hi-Hi
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
OUT1 set value : OUT1 ON
Measurement value
OUT2 set value : OUT2 ON
(LO-LO)
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
Measurement value
OUT1 set value : OUT1 ON
Measurement value
OUT2 set value : OUT2 ON
(LO-HI)
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
(HI-LO)
Measurement value OUT1 set value : OUT1 ON
Measurement value
OUT2 set value : OUT2 ON
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
(HI-HI)
Measurement value
OUT1 set value : OUT1 ON
Measurement value
T2
t v
l
:
T2
N
Delay time after switching on the power
: The tachometer will start to run when the set delay time is due
after the power is switched on. (Range of delay time: 0.1 ~ 99.9 secs.)
Setup average value of input filter
: Range for obtaining average (n = 0 ~ 3). This parameter obtains the
average of 2
n
input data for more stable output value.
VARITEL INGENIERIA ELECTRONICA S.A.
info@varitel.com - www.varitel.com - Tel. (54) 11-4243-1171 / Fax: (54) 11-4292-7545
Manuel Baliña 456, Lomas de Zamora (B1832CCJ) Buenos Aires, Argentina.