C.1 EMC Standards for an ES3/EX3/SV3/SX3 Series System
C.1.1 DVP-ES3/EX3/SV3/SX3 Series System EMC Standards
The EMC standards that are applicable to a DVP-ES3/EX3/SV3/SX3 series system are listed in the following
tables.
EMI
Port Frequency range Level (Normative) Reference standard
Enclosure port
(radiated)
(measured at a
distance of 10 meters)
30-230 MHz 40 dB (μV/m) quasi-peak
IEC 61000-6-4
230-1000 MHz 47 dB (μV/m) quasi-peak
AC power port
(conducted)
0.15-0.5 MHz
79
dB (μV) quasi-peak
IEC 61000-6-4
66 dB (μV) average
0.5-30 MHz
73 dB (μV) quasi-peak
60 dB (μV) average
EMS
Environmental
phenomenon
Reference
standard
Test Test level
Electrostatic
discharge
IEC 61000-4-2
Contact ± 4 kV
Air ± 8 kV
Radio frequency
electromagnetic field
Amplitude modulated
IEC 61000-4-3
80% A
M,
1 kHz sinusoidal
2.0-2.7 GHz 1 V/m
1.4-2.0 GHz 3 V/m
2.0-2.7 GHz 3 V/m
2.7-6.0 GHz 3 V/m
Power frequency
magnetic field
IEC 61000-4-8
60 Hz 30 A/m