Chapter 12 Description of Parameter SettingsCP2000 
 
 
12.1-06-26 
 
 
Enable Bypass on Fire Mode 
   
 
  Default: 0 
    Settings  0: Disable Bypass 
1: Enable Bypass   
 
 
Bypass Delay Time on Fire Mode 
   
 
  Default: 0.0 
    Settings  0.0–6550.0 sec. 
 
 
 
Number of Times of Reset in Fire Mode 
   
 
  Default: 0 
    Settings  0–10   
 
 
Length of Time of Reset in Fire Mode 
   
 
  Default: 60.0 
    Settings  0.0–6000.0 sec. 
  The  settings  for  Pr.06-82  to  Pr.06-85  determine  whether  to  switch  motors  to  operate  under 
mains electricity when in fire mode. 
 
 
Fire Mode Motion 
   
 
  Default: 0 
    Settings  bit0: 0=Open Loop; 1=Close Loop (PID control) 
bit1: 0=Manual reset fire mode; 1=Auto reset fire mode 
0:
 Open loop control & manual reset fire mode 
1: Close loop control & manual reset fire mode
 
2: Open loop control & auto reset fire mode 
3: Close loop control & auto reset fire mode 
 
 
Fire Mode PID Set Point 
   
 
  Default: 0.00 
    Settings  0.00–100.00% 
  Use Pr.06-87 as the Fire mode PID set point when setting the Pr.06-86 bit0=1.