Chapter 7 Optional AccessoriesCP2000
7-40
Model
kW HP
Rated Amps of
AC Reactor (Arms)
Max. continuous
Amps (Arms)
3% impedance (mH) 5% impedance (mH)
Normal Duty Light Duty Normal Duty Light Duty Normal Duty Light Duty Normal Duty Light Duty
3150 315 425 290 350 435.0 420.0 0.131 0.109 0.219 0.181
4000 400 530 350 430 525.0 516.0 0.109 0.088 0.181 0.147
4500 450 600 385 465 577.5 558.0 0.099 0.082 0.165 0.136
5600 560 745 465 590 697.5 708.0 0.082 0.064 0.136 0.107
6300 630 850 675 675 1012.5 810.0 0.056 0.056 0.094 0.094
Table 7-49