Chapter 12 Description of Parameter SettingsCP2000   
 
12.1-00-8 
Permanent Magnetic Motor Space Vector Control (PMSVC) 
 
 
 
Load Selection 
 
 
  Default: 0 
  Settings  0: Light load 
    1: Normal load 
  Light load (230V & 460V series): over-load rated output current 120% in 60 seconds. Refer to 
Pr.00-17 for the setting for the carrier wave. Refer to Pr.00-01 or the specification table in Section 
09 for the rated current. 
 Normal  load  of  230V  &  460V:  over-load  rated  output  current  120%  in  60  seconds  (160%,  3 
seconds).  Refer  to  Pr.00-17  for  the  setting  for  the  carrier  wave.  Refer  to  Pr.00-01  or  the 
specification table in Section 9 for the rated current. 
  Pr.00-01 varies with the setting value for Pr.00-16. The default value and maximum setting value 
for Pr.06-03 and Pr.06-04 also vary with the setting value for Pr.00-16. 
 
 
Carrier Frequency 
  
   
  Default: Table below 
  Settings  2–15 kHz 
 This parameter determinates the PWM carrier frequency for the AC motor drive. 
230V 
Settings  2–15 kHz  2–10 kHz  2–9 kHz 
Light Load 
Models  1–20 HP [0.75–15 kW]  25–60 HP [18.5–45 kW]  75–125 HP [55–90 kW] 
Default  8 kHz  6 kHz  4 kHz 
Normal 
Load 
Models  0.5–15 HP [0.4–11 kW]  20–50 HP [15–37 kW]  60–100 HP [45–75 kW] 
Default  8 kHz  6 kHz  4k Hz 
 
460V   
Settings  2–15 kHz  2–10 kHz  2–9 kHz 
Light Load 
Models  1–25 HP [0.75–18.5 kW]  30–100 HP [22–75 kW]  125–536 HP [90–400 kW] 
Default  8 kHz  6 kHz  4 kHz 
Normal 
Load 
Models  0.5–20 HP [0.4–15 kW]  25–75 HP [18.5–55 kW]  100–475 HP [75–355 kW] 
Default  8 kHz  6 kHz  4 kHz