Chapter 12 Description of Parameter SettingsCP2000 
 
 
12.1-06-22 
(2)  Select one of the voltage type analog inputs below:   
(a) AVI1(Pr.03-00=11) 
(b) AVI2 (Pr.03-02=11) 
(c) ACI (Pr.03-01=11 and Pr.03-29=1). 
(3)  When  selecting  Pr.03-01=11  and  Pr.03-29=1,  you  must  switch  SW4  to  0–10  V  for  the 
external I/O board.   
(4)  The  AFM2  outputs constant voltage  or  current,  the Pr.03-23=23.  You  must  switch  AFM2 
SW2  to  0–20  mA  for  the  external  I/O  board,  and  set  AFM2  output  level  to  45% 
(Pr.03-33=45%) of 20 mA = 9 mA.     
(5)  Use  Pr.03-33  to  adjust  the  constant  voltage  or constant current  of  the  AFM2  output, the 
setting range is 0–100.00%.   
(6)  There  are  two  types  of  action  levels  for  PT100.  The  diagram  below  shows  the  PT100 
protecting action:   
 
(7)  PT100 wiring diagram:   
 
 
 
 
 
Figure 1