Chapter 11 Summary of Parameter Settings | VFD-ED
11-24
Pr. Parameter Name Setting Range Default
VF
VFPG
SVC
FOCPG
FOCPM
direction detection when in normal
mode.
06-47
Power Generation
Direction Search Time
0.0–5.0 sec. 1.0 ○ ○ ○ ○ ○
06-48
Power Capacity of
Emergency Power (EPS)
0.0–100.0 kVA 0.0 ○ ○ ○ ○ ○
06-49
STO Latch Selection
0000h: STO fault latched, resending
RUN command is required
0001h: STO warning latched, resending
RUN command is required
0002h: STO fault latched
0003h: STO warning unlatched
0000h ○ ○ ○ ○ ○
06-50
MO’s Action when
Retrying after Fault
0: Output
1: No output
0 ○ ○ ○ ○ ○
06-51
Number of Times to Retry
after Fault
0–10 0 ○ ○ ○ ○ ○
06-52
Time Interval between
Retries
0.5–600.0 sec. 10.0 ○ ○ ○ ○ ○
06-53
Frequency Command
when the Most Recent
Fault Occurred
0.00–655.35 Hz
Read
only
○ ○ ○ ○ ○
06-54
Output Frequency when
the Most Recent Fault
Occurred
0.00–655.35 Hz
Read
only
○ ○ ○ ○ ○
06-55
Output Current when the
Most Recent Fault
Occurred
0.00–655.35 Amps
Read
only
○ ○ ○ ○ ○
06-56
Motor Frequency when
the Most Recent Fault
Occurred
0.00–655.35 Hz
Read
only
○ ○ ○ ○ ○
06-57
Output Voltage when the
Most Recent Fault
Occurred
0.0–6553.5 V
Read
only
○ ○ ○ ○ ○
06-58
DC Bus Voltage when
the Most Recent Fault
Occurred
0.0–6553.5 V
Read
only
○ ○ ○ ○ ○
06-59
Output Power when the
Most Recent Fault
Occurred
0.0–6553.5 kW
Read
only
○ ○ ○ ○ ○
06-60
Output Torque when the
Most Recent Fault
Occurred
0.00–655.35%
Read
only
○ ○ ○ ○ ○
06-61
IGBT Temperature when
the Most Recent Fault
Occurred
-3276.8–3276.7ºC
Read
only
○ ○ ○ ○ ○
06-62
Multi-input Terminals
0000h–FFFFh
Read
○
○
○
○
○