Chapter 8 Option CardsMS300 
160 
 
1.  Broken communication 
2.  MAC ID test failure 
3.  No network power supply. 
4.  CMM-DN02 is off-line. 
1.  Make  sure  all  MAC  IDs  on  the  network  are 
unique. 
2.  Check if the network installation is normal. 
3.  Check if the baud rate of the CMM-DN02 is the 
same as that of the other nodes. 
4.  Check if the node address of the CMM-DN02 
is illegal. 
5.  Check if the network power supply is normal. 
No power supply or device is off-line 
Check the power supply of the CMM-DN02 and see 
if the connection is normal. 
Switch the master PLC to RUN status. 
1.  Reset the CMM-DN02. 
2.  Re-power the AC motor drive. 
1.  See the fault codes displayed on the keypad and 
find the causes. 
2.  Return the unit to the factory for repair if 
necessary. 
The CMM-DN02 is connecting with 
the AC motor drive. 
If the flashing lasts for a long period of time, turn off 
the power to check if the CMM-DN02 and the AC 
motor drive install correctly and are normally 
connected to each other.