Chapter 1 IntroductionMS300 
 
8 
 
suppression. If in doubt, install an extra electrostatic shielded cable on the power supply side 
between the main circuit and the control terminals to increase shielding. 
Asymmetric Ground System (Corner Grounded TN Systems) 
Caution: Do not remove the RFI jumper while power to the input terminal of the drive is ON. 
In the following four situations, you must remove the RFI jumper. This is to prevent the system from 
grounding through the RFI and filter capacitors and damaging the drive. 
You must remove the RFI jumper for an asymmetric ground system 
1. Grounding at a corner in a triangle configuration 
   
2. Grounding at a midpoint in a polygonal 
configuration   
 
3. Grounding at one end in a single-phase 
configuration   
4. No stable neutral grounding in a three-phase 
autotransformer configuration   
You can use the RFI jumper for a symmetrical grounding power system 
In a situation with a symmetrical grounding power system, you 
can use the RFI jumper to maintain the effect of the built-in EMC 
filter and surge absorber. For example, the diagram on the right 
is a symmetrical grounding power system.