Chapter 8 Option CardsMS300 
162 
 
Environment 
ESD (IEC 61800-5-1, IEC 61000-4-2) 
EFT (IEC 61800-5-1, IEC 61000-4-4) 
Surge Test (IEC 61800-5-1, IEC 61000-4-5) 
Conducted Susceptibility Test (IEC 61800-5-1, IEC 61000-4-6) 
Operation: -10–50°C (temperature), 90% (humidity) 
Storage: -25–70°C (temperature), 95% (humidity) 
Shock / Vibration Resistance 
International standards:   
IEC 61800-5-1, IEC 60068-2-6 / IEC 61800-5-1, IEC 60068-2-27 
8-4-4 Installation 
Connecting the CMM-EIP02 to the Network 
1.  Turn off the power of the drive. 
2.  Open the front cover of the drive. 
3.  Connect the CAT-5e network cable to the RJ45 port of the 
CMM-EIP02 (as shown in the right figure). 
Positive pole for data 
transmission 
Negative pole for data 
transmission 
Negative pole for data 
reception 
Positive pole for data 
reception 
8-4-5 MS300 Communication Parameter Settings when Connecting to Ethernet 
When you connect the MS300 to Ethernet, set up the communication parameters based on the table 
below. The Ethernet master reads and writes the frequency command words and operation command 
words after you set the communication parameters. 
Master frequency 
command source 
The frequency command is controlled by the 
communication card. 
The operation command is controlled by the 
communication card. 
Communication 
decoding method 
The decoding method for Delta AC motor 
drive. 
0: Static IP 
1: Dynamic IP (DHCP)