Recommended specifications and models for crimping tool:   
CRIMPFOX 10S - 1212045, Manufacturer: PHOENIX CONTACT 
DNT13-0101, Manufacturer: DINKLE 
+24 V
DC
 ± 10 % 100 mA 
When used in parallel, if the +24V terminal is used with a 
feedback sensor, unequal current may occur, and there will 
be a risk of failure.   
Refer to Pr.02-01–02-07 to program the multi-function 
inputs MI1–MI7. 
Source Mode 
ON: activation current is 3.3 mA and the voltage is 11 V
DC
 
OFF: cut-off voltage ≤ 5 V
DC
 
Sink Mode 
ON: activation current is 3.3 mA and the voltage is 13 V
DC
 
OFF: cut-off voltage ≥ 19 V
DC
 
  When Pr.02-00 = 0, MI1 and MI2 can be programmed. 
  When Pr.02-00 ≠ 0, the functions of MI1 and MI2 act 
according to Pr.02-00 setting. 
  When Pr.02-07 = 0, MI7 is pulse input terminal. 
  MI7 uses pulse input, and the maximum input 
frequency = 33 kHz. You can use it as frequency 
command source or connect it to the encoder for motor 
closed-loop control. 
  MI7 motor closed-loop control only supports VFPG 
control mode.