EasyManuals Logo

Delta VFD2A7MS43ANSAA User Manual

Delta VFD2A7MS43ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #246 background imageLoading...
Page #246 background image
Chapter 11 Summary of Parameter SettingsMS300
237
Pr.
Explanation
Settings
Default
06-30
PTC Level
0.0–100.0%
50.0
06-31
Frequency Command at
Malfunction
0.00–599.00 Hz
Read only
06-32
Output Frequency at
Malfunction
0.00–599.00 Hz
Read only
06-33
Output Voltage at
Malfunction
0.0–6553.5 V
Read only
06-34
DC bus Voltage at
Malfunction
0.0–6553.5 V
Read only
06-35
Output Current at
Malfunction
0.00–655.35 Amp
Read only
06-36
IGBT Temperature at
Malfunction
-3276.7–3276.7
o
C
Read only
06-38
Motor Speed at
Malfunction
-32767–32767 rpm
Read only
06-39
Torque Command at
Malfunction
-32767–32767%
Read only
06-40
Status of the Multi-
Function Input Terminal at
Malfunction
0000h–FFFFh
Read only
06-41
Status of the Multi-
Function Output Terminal
at Malfunction
0000h–FFFFh
Read only
06-42
Drive Status at
Malfunction
0000h–FFFFh
Read only
06-44
STO Latch Selection
0: STO latch
1: STO no latch
0
06-45
Output Phase Loss
Detection Action (OPHL)
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
3
06-46
Detection Time for Output
Phase Loss
0.000–65.535 sec.
0.500
06-47
Current Detection Level
for Output Phase Loss
0.00–100.00%
1.00
06-48
DC Brake Time for Output
Phase Loss
0.000–65.535 sec.
0.000
06-49
Lvx Auto-Reset
0: Disable
1: Enable
0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A7MS43ANSAA and is the answer not in the manual?

Delta VFD2A7MS43ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A7MS43ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals