Chapter 12 Descriptions of Parameter SettingsMS300
282
01-04
Mid-point Voltage 1 of Motor 1
Default: 11.0 / 22.0 / 40.0
Settings
115V / 230V models: 0.0–240.0 V
460V models: 0.0480.0 V
575V models: 0.0–600.0 V
01-37
Mid-point Frequency 1 of Motor 2
12-1-1-1
Default: 3.00
Settings
0.00–599.00 Hz
01-38
Mid-point Voltage 1 of Motor 2
Default: 11.0 / 22.0 / 40.0
Settings
115V / 230V models: 0.0–240.0 V
460V models: 0.0480.0 V
575V models: 0.0600.0 V
01-56
Mid-point Frequency 1 of Motor 3
Default: 3.00
Settings
0.00–599.00 Hz
01-57
Mid-point Voltage 1 of Motor 3
Default: 11.0 / 22.0 / 40.0
Settings
115V / 230V models: 0.0–240.0 V
460V models: 0.0480.0 V
575V models: 0.0–600.0 V
01-65
Mid-point Frequency 1 of Motor 4
Default: 3.00
Settings
0.00–599.00 Hz
01-66
Mid-point Voltage 1 of Motor 4
Default: 11.0 / 22.0 / 40.0
Settings
115V / 230V models: 0.0–240.0 V
460V models: 0.0480.0 V
575V models: 0.0–600.0 V
01-05
Mid-point Frequency 2 of Motor 1
Default: 1.50
Settings
0.00–599.00 Hz
01-06
Mid-point Voltage 2 of Motor 1
Default: 5.0 / 10.0 / 26.1
Settings
115V / 230V models: 0.0240.0 V
460V models: 0.0480.0 V
575V models: 0.0–600.0 V
01-39
Mid-point Frequency 2 of Motor 2
Default: 1.50
Settings
0.00–599.00 Hz