EasyManua.ls Logo

Delta VFD2A7MS43ANSAA

Delta VFD2A7MS43ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Descriptions of Parameter SettingsMS300
305
When Pr.02-09 is set to 0:
The increasing or decreasing Frequency command (F) operates according to the setting for
acceleration or deceleration time (refer to Pr.01-1201-19).
When Pr.02-09 is set to 1:
The increasing or decreasing Frequency command (F) operates according to the setting of
Pr.02-10 (0.001–1.000 Hz/ms).
When Pr.02-09 is set to 2:
The increasing / decreasing frequency command (F) operates according to the pulse of Pr.02-
10.

Table of Contents

Related product manuals