Chapter 12 Descriptions of Parameter SettingsMS300
435
All control modes are based on 100% of the motor rated current except:
IM: VF, VFPG, SVC
PM: PMSVC
11-21
Flux Weakening Curve for Motor 1 Gain Value
Default: 90
Settings
0–200%
11-22
Flux Weakening Curve for Motor 2 Gain Value
Default: 90
Settings
0–200%
Adjusts the output voltage for the flux weakening curve.
For the spindle application, use this adjustment method:
1. Run the motor to the highest frequency.
2. Observe the output voltage.
3. Adjust the Pr.11-21 (motor 1) or Pr.11-22 (motor 2) setting to make the output voltage reach
the motor rated voltage.
4. The larger the setting value, the greater the output voltage.