EasyManuals Logo

Delta VFD2A7MS43ANSAA User Manual

Delta VFD2A7MS43ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #671 background imageLoading...
Page #671 background image
Chapter 16 PLC Function ApplicationsMS300
662
Digital keypad (KPMS-LE01)
Figure 16-6
Select PLC1 to enter PLC mode setting (see Figure 16-6).
PLC 0: Do not implement PLC functions
PLC 1: Initiate PLC Run
PLC 2: Initiate PLC Stop
The MS300 automatically switches to PLC mode when the external multi-function input terminals
(MI1–MI7) are in PLC Mode selection bit 0 (51) or PLC Mode selection bit1 (52), and the terminal
contact is closed or open. In this case, keypad switching is invalid. The corresponding actions are
listed in Table 16-2.
PLC mode
PLC Mode selection
bit1 (52)
PLC Mode selection
bit0 (51)
Using KPC-CC01
(optional)
Using KPMS-LE01
Disable
PLC 0
OFF
OFF
PLC Run
PLC 1
OFF
ON
PLC Stop
PLC 2
ON
OFF
Maintain previous state
Maintain previous state
ON
ON
Table 16-2
Using the MS300 digital keypad to implement the PLC functions
When the PLC screen from the keypad is set to PLC0 (or “Disableon KPC-CC01), the
built-in PLC is disabled and you cannot use WPLSoft or ISPSoft to connect to it.
When the PLC screen from the keypad is set to PLC1 (or “PLC Runon KPC-CC01), the
built-in PLC is enabled and you can use WPLSoft or ISPSoft to connect to it through
Modbus.
When the PLC screen from the keypad is set to PLC2 (or “PLC Stopon KPC-CC01), the
built-in PLC is enabled and you can use WPLSoft or ISPSoft to connect to it. However, the
programs in the built-in PLC do not work.
When the built-in PLC is enabled (PLC1 or PLC2), you can switch between PLC Run or
PLC Stop through WPLSoft or ISPSoft.
The external terminal control method is the same as shown in Table 16-2 above.
NOTE:
When the input / output terminals (MI1–MI7, Relay, and MO) are included in the PLC program, these
input / output terminals are used only by the PLC. For example, when the PLC program controls Y0
during PLC operation (PLC1 or PLC2), the corresponding output terminal relay (RA / RB / RC)
operates according to the program. At this time, the multifunctional input / output terminal setting has
no effect. Because these terminal functions are already being used by the PLC, you can determine
the DI / DO / AO in use by the PLC by looking at Pr.02-52, 02-53, and 03-30.
When the PLC program uses special register D1040, the corresponding AO contact AFM is occupied.
Pr.03-30 monitors the action state of the PLC function analog output terminals; bit 0 corresponds to
the AFM action state.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A7MS43ANSAA and is the answer not in the manual?

Delta VFD2A7MS43ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A7MS43ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals