EasyManuals Logo

Delta VFD2A7MS43ANSAA User Manual

Delta VFD2A7MS43ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #721 background imageLoading...
Page #721 background image
Chapter 16 PLC Function ApplicationsMS300
712
API
MOV
S D
Move data
12
D
P
bit device
Word device
16-bit command (5 STEP)
MOV
Continuous
execution type
MOVP
Pulse
execution type
32-bit command (9 STEP)
DMOV
Continuous
execution type
DMOVP
Pulse
execution type
Flag signal: none
X
Y
M
K
H
KnX
KnY
KnM
T
C
D
S
D
Notes on operand usage: none
S: Data source. D: Destination of data movement.
Moves the content in S to D. When the command does not execute, the content
of D does not change.
When X0 = OFF, the content of D10 does not change; if X0 = ON, the value K10
is moved to data register D10.
When X1 = OFF, the content of D10 does not change; if X1 = ON, the current
value of T0 is moved to data register D10.
X0
K10MOV D0
X1
T0MOV D10

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A7MS43ANSAA and is the answer not in the manual?

Delta VFD2A7MS43ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A7MS43ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals