Chapter 16 PLC Function ApplicationsMS300
754
Floating point number contact form compare LD*
Continuous
execution type
Notes on operand usage: ※,:, =, >, <, <>, ≤, ≥
Refer to the function specifications table for each device in series
for the scope of device usage.
S
1
: data source device 1. S
2
: data source device 2.
This command compares the contents of S
1
and S
2
. Taking "FLD=" as an
example, if the result of comparison is “equal”, this command activates; but it
does not activate when the result is “unequal”.
The FLD* command can directly input floating point numbers (for instance:
F1.2) to the S
1
, S
2
operands, or store floating point numbers in register D for
use in operations.
You can use this command while directly to connect with the busbar
Conditions for
Activation
Conditions for
Inactivation
When the floating point number in register D200 (D201) is less than or equal to
F1.2, and X1 is activated, then contact Y21 activates and remains in that state.