© Radionics Inc. reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.
8
17 18 19 20 21 22 23 24 25 26 27 28 29 30
PO1
PO2 1 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - L + L + L + L +
ZONES 1-8 : Intended for connection of Normally Open or
Normally Closed alarm contacts. May be used for compatible
2-wire smoke detectors. These zones require a 2.21KW resistor
(P/N 25899) at the end of the loop.
Power is momentarily removed from L+ after a [PIN]+[System
Reset] or during fire verification.
Zone 1-8 assignments are programmed in addresses 0018-0025.
PROGRAMMABLE OUTPUTS:
PO1 shorts to aux. power negative when activated. PO1 can sink up to 1.0A.
PO1 function programmed in address 0147.
PO2 supplies 12 V and up to 500 mA when activated.
PO2 function programmed in address 0148.
DS7400Xi Panel Wiring & Programming