Disconnect wire jumper from terminal 4 to inner housing of Bell Box.
(Prevents a ground fault condition)
Connect wiring between control and Bell Box as shown next slide.
To use AB-12 Bell/Housing, cut jumper wire “JP1” on control.
EOL used in AB-12 Bell / Housing must be 27K ohms.
Program Zone 8 as 24-hour zone by programming it to follow zn function 7.
(Program address 0025 should be 07)
Do not change default programming of zone function 7.
(Program address 0007 should be 22)
Wiring & Programming for Installations
using Ademco AB-12 Housing
DS7400Xi Panel Wiring & Programming