EasyManua.ls Logo

DGS 101 User Manual

Default Icon
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
TECHNOLOGIES
Technical Sheet
ref C1540 J
GDS 101
SINGLE POINT GAS ALARM
Operation
A fixed single point alarm unit that meets the requirements for continuous economic and reliable monitoring of gas levels in a
wide range of environments from commercial premises through to heavy industrial applications that may require hazardous
area sensing. The GDS101 may be utilised as a standalone unit or as an addressable sensor forming part of the GDS Combi
CANbus addressable network system and therefore offering the features of our most advanced system.
Typical monitor locations are – public buildings, boiler plant rooms, swimming pools, water treatment works, H&V control
systems, manufacturing and process plants.
Installation
CONTROL UNIT: The control unit should be mounted in a position which is
accessible and in the field of vision.
Mains should be from a fused supply.
SENSORS: The positioning of sensors depends upon the type of gas to be
monitored and its density with respect to air.
HEAVY GASES (LPG, Propane, Butane, Refrigerant Gases) – locate at 15
to 20 cm from the floor.
LIGHTER GASES (Methane, Natural Gas, Town Gas) –
locate at 5 to 10cm from the ceiling.
CARBON MONOXIDE – locate at 1.5 metres above floor level.
All equipment should be mounted away from direct heat and in
accordance with its IP rating.
Initial Set–up Procedure
Having terminated all cables switch on the power and wait for the 1 minute
stabilisation period to complete, this is indicated by the power and inhibit
indicator changing from flashing to a steady state, a reduced power mode
feature is activated one hour following any operator activity, this state is
indicated by a screen power reduction of approximately 50%, pressing
any button will return the screen to full display.
The alarm panel may have been supplied without a sensor and a customer
supplied device is to be used, in this case the following adjustments should
be carried out. Adjust jumpers as follows:
For 24DC (+ sig –) 4~20mA sensor devices connect jumpers
J5/11 Position A, J12 Off, J14 link B.
For catalytic sensors (W Y P) J5/11 Position B, J12 On, J14 Link A.
(Caution reset link J14 to position A before connecting the sensor
as damage will occur requiring sensor replacement).
Sensor supply may be measured between the two sensor voltage test pins,
adjust as required using the sensor supply adjustment potentiometer. See
sensor cell supply table.
Test pins TP6/TP7 may be used to check 4~20mA sensor input signals 4mV
= 4mA.
Measuring across TP8/TP9 will allow the 4~20mA output signal to be
checked 4mV = 4mA. Output for pellistor (flammable) can be adjusted
using 4+20mA pots.
Changes to gas type and range can be made by connecting GDS RS232
pod to J3 and using a PC running hyper terminal at 4800 baud.
The Hyper Terminal output screen shows continuous data output/
commands and allows input from the PC keyboard pressing ‘C’ enters
calibration mode, press ‘G’ to change the gas type to match the cell being
used. Note – the range of the new gas has a default value but can be
adjusted by pressing ‘R’.
For catalytic sensors course zero adjustment is achieved by turning the zero
potentiometer (10 turn) until the zero LED just turns off.
Access to the Menu
The GDS101 is supplied with factory set default settings which may be
re-adjusted from the front screen and push buttons:
Press 2 to access the menu followed by 231, menu entry will be at level 5
(Exit), pressing 1 or 3 will enable travel through the sub menus 1–9 and
adjustment of settings, pressing 2 enables access into each sub menu and
on completion pressing 2 will confirm your selection and move to the next
setting.
1. Zero/Span – In clean air Zero display – apply test gas at the peak
reading and adjust the span.
2. Alarm Levels – 3 alarm levels. Pressing 1+3 together will cycle through
rising and falling alarms and latched (L) or unlatched (U) (auto reset)
relays in following order
(
) L, ( ) U, ( ) U, ( ) L. Default setting latched.
3. Alarm Delay – Time to alarm in seconds
(default setting 2 seconds) maximum 255 seconds.
4. Inhibit Alarm – Isolate alarm functions – maintenance and test periods.
Second part of this menu allows YES/NO selection of sounder alert for
alarm A1.
5. Exit Press 2 – Entry and Exit point of menu.
6. L.C.D Brightness – Adjustment of display brightness.
7. L.E.D/Relay Test – Turns indicators and relays ON.
8. Auto Zero – Use only when very low alarm levels are required
(<10% of scale).
9. Sensor Address – Used when connecting to a GDS
Combi system.
A. 4~20mA output adjust (Tox/O
2
only). Pressing 1 or 3 will allow for
output to be adjusted to 4mA and 20mA as measured on test pins 8+9.
B. To set A1 alarm relay to become a global sounder relay with a 10min
time delay after alarm condition ends. Press 1 to active or press 3 to
deactivate.
C. To delay relay deactivation after alarm condition has ceased, press
2 to cycle through alarms A1,A2 and A3. when the required alarm is
displayed press 1 to increase the delay and 3 to decrease the delay.
D. Allows relay A3 to change from alarm relay to valve timer central relay
E. Relay on time, minimum 2 minutes maximum 200 mins.
F. Relay off time, minimum 2 minutes maximum 200 mins.
E: sales@gds-technologies.co.uk T: +44 (0)113 286 0166
GDS TECHNOLOGIES LTD | FUSION POINT | ASH LANE | GARFORTH | LEEDS | LS25 2GA | UK www.gds-technologies.co.uk
Question and Answer IconNeed help?

Do you have a question about the DGS 101 and is the answer not in the manual?

DGS 101 Specifications

General IconGeneral
BrandDGS
Model101
CategorySecurity System
LanguageEnglish

Summary

Operation

Installation and Setup

Control Unit Mounting

Mount the control unit in an accessible location within the field of vision.

Sensor Positioning

Position sensors based on gas type and density relative to air.

Initial Set-up Procedure

Describes power-on stabilization, jumper adjustments for sensors, and signal measurement.

Gas Type and Range Configuration

Configure gas type and range via PC using Hyper Terminal at 4800 baud.

Catalytic Sensor Zero Adjustment

Achieve course zero adjustment for catalytic sensors using the zero potentiometer.

Accessing and Configuring the Menu

Menu Navigation

Access menu by pressing 2, navigate submenus 1-9 using 1 or 3, confirm with 2.

Zero and Span Calibration

Calibrate zero in clean air and span using test gas at peak reading.

Alarm Level Settings

Configure 3 alarm levels, cycling through rising/falling and latched/unlatched relays.

Alarm Delay Configuration

Set alarm delay time in seconds, with a maximum of 255 seconds.

Inhibit Alarm Functionality

Isolate alarms for maintenance/test periods and select sounder alert option.

Display and Relay Testing

Adjust LCD brightness, test indicators, and relays.

Auto Zero and Sensor Addressing

Use Auto Zero for low alarm levels and set sensor address for Combi system.

Analog Output Adjustment

Adjust 4-20mA output for Tox/O2 sensors between 4mA and 20mA.

Alarm Relay and Time Delay Settings

Configure A1 relay as global sounder, delay relay deactivation, and set relay on/off times.

Specifications and Environmental Data

Power Supply Versions

Details for Mains (230/115v AC) and DC (24v DC) versions.

Outputs and Connectivity

Information on alarm/fault relays, CANbus, and 4-20mA analogue output.

Indicators and Display

Description of status LEDs (Power, Alarms, Fault) and the alpha-numeric display.

Audible Alarm

Details on gas/fault muting and sound level.

Environmental Conditions

Specifies operating temperature, storage temperature, humidity, and IP rating.

Sensor Cable Requirements

Details on the 3-core screened cable and maximum length.