Anomaly INTERVENTION OF THE USER’S MAIN SWITCH
Cause Remedy
Compressor: short circuit and/or low dielectric
strength
Replace the component
Pump: short circuit and/or low dielectric strength Replace the component
Hot gas valve: short circuit and/or low dielectric
strength
Replace the component
Thermostat: low dielectric strength Replace the component
Other electrical components: short circuit and/or
low dielectric strength
Replace the component
Anomaly ICE PRODUCTION DECREASE
Cause Remedy
Condenser or air filter clogged Clean the filter and the condenser
Bin flooded Check the water outlet pipes
Ice maker without refrigerant Find the leak, repair it, make vacuum and charge
Refrigerant blow-by through the hot gas valve Clean the valve or replace it
Water blow-by through the evaporator water inlet
valve
Replace the valve
The compressor doesn’t compress Replace the compressor