EasyManua.ls Logo

Dicon 650M - User Manual

Dicon 650M
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
SMOKE ALARMS
& HEAT ALARMS
A: GUIDANCE ON INSTALLATION
WARNING: Wiring should be installed by a qualified electrician in accordance with BS7671.
Permanent connection to the fixed wiring of the building should be made in a suitable junction box.
This alarm must not be exposed to dripping or splashing. Connect the alarm as late as possible in
an installation, particularly in new build, to avoid contamination. Remove the dust cover before
applying power.
NOTE: For detailed guidance on the siting of this alarm refer to section C of this handbook.
IMPORTANT: The circuit used to power the alarm must be a 24 hour voltage circuit that cannot be
turned off by a switch. BS5839 Part 6 states that: -
For mains powered alarms, each with an integral standby supply (Grade D), the mains electricity
supply should take the form of either:
a) an independent circuit at the dwelling’s main circuit board, in which case no other electrical
equipment should be connected to this circuit (other than a dedicated monitoring device
installed to indicate failure of the mains electricity supply to the alarms); or
b) a separately electrically protected, regularly used local lighting circuit.
For mains powered alarms, with no standby supply (Grade E), the mains electricity supply may
only take the form of an independent circuit as per a) above. If it is necessary to use an RCD for
protection, it should operate independently of any RCD protection for circuits supplying sockets or
portable equipment.
All interconnected alarms should be installed on a single final circuit.
NOTE: The maximum interconnect wiring length is 250 metres. The maximum number of alarms
interconnected together is 12. Dicon smoke alarms should not be connected to any model
produced by another manufacturer.
The location of the alarms must comply with the applicable building codes and the advice in
section C: WHERE TO LOCATE below.
B: INSTALLATION (See Diagrams 1 & 2)
1. IMPORTANT INFORMATION: THE COLOUR CODING FOR ELECTRICAL CABLES USED IN
BUILDING WIRING HAS BEEN CHANGED AS FOLLOWS:-
Old colour New (harmonised) colour Designation
Red Brown L1 (Live)
Yellow Black L2 (Live)
Blue Grey L3 (Live)
Black Blue Neutral
The new (harmonised) colour cables may be used on site from 31 March 2004. New installations
or alterations to existing installations may use either new or old colours, but not both, from 31st
March 2004 until 31st March 2006. Only the new colours may be used after 31 March 2006. For
more information see Amendment No: 2 to BS 7671:2001 and guidance publications.
See also www.iee.org/cablecolours
When selecting cable for connecting interlinked
smoke alarms the interlink wire should be
treated as live.
2. Use either of the methods of installation
shown in diagrams1 and 2.
The installation method shown in diagram 1 is
suitable for a plasterboard or similar ceiling
where access to the void behind it is available
and suitable to mount the junction box.
The installation method shown in diagram 2 is
suitable for concrete or similar ceilings where
access is insufficient or where surface wiring
is necessary.
3. Connect the brown wire to the brown (live)
in the house wiring and the blue wire to the
blue (neutral). NO CONNECTION SHOULD
BE MADE TO THE MAINS ELECTRICITY
SUPPLY EARTH TERMINAL. TERMINATE
HOUSE WIRING EARTH
IN SPARE CONNECTOR.
4. For multiple alarm installations use a “three
core and earth” style cable between all the
alarms to be interconnected and connect
the third core of that cable to the white wire from the smoke alarm. DO NOT use the earth wire
for the interconnect line. This must be treated as live, i.e. insulated and sheathed. If the alarm
is not going to be interconnected, cap the unused wires.
5. Remove the baseplate from the back of the alarm by twisting anti-clockwise as far as it will go.
(about 12 mm). Detach the locking pin.
CHECKS BEFORE USE
370MBX, 650MBX, 670MBX, and 680MBX:
• Check battery has been fitted correctly.
• Check alarm is not beeping.
• Test alarm before switching on the electricity supply.
All Alarms:
• Check the green light is on (behind the front grille).
• Check the red light flashes every 45 seconds or so.
• When testing linked alarms check that they all
interconnect within 10 seconds.
IMPORTANT NOTES
• On the 370MBX the alarm will beep for 10 minutes
if the pause button has been pressed.
• Alarms with rechargeable batteries or capacitor
back up may beep for up to 2 hours while the
batteries / capacitors charge.
• Leave a copy of this handbook with the user and ensure
they know how to use and maintain the alarm.
650MBX, 670MBX and 680MBX
Detach battery door screw from the base plate.
Open the battery door on the back of the alarm,
connect the battery, close the door and secure
with the screw provided before fitting the alarm
to the baseplate.
Test the alarm using the test button.
6. Attach the flat side of the mounting plate and
tighten screws to fit snugly against the pattress
or junction box and ceiling or wall.
7. Bring the power connector through the centre
opening of the plate.
IMPORTANT: THE PAPER GASKET SUPPLIED MUST
BE FITTED BETWEEN THE REAR OF THE ALARM
AND THE MOUNTING PLATE TO PREVENT THE
ALARM FROM BECOMING CONTAMINATED BY
DUST AND TO ENSURE THE CORRECT OPERATION
OF THE ALARM. Gasket not required on alarms fitted
with protective film on the back.
8. Plug the lead into the rear of the alarm.
9. Place the alarm on the baseplate by lining up
arrows on the baseplate and the alarm rim and
twist clockwise to fasten.
To secure the alarm to the baseplate, insert the
locking pin (removed from the base in 5 above)
into the ‘T’ shaped slot located above the arrow
on the rim of the alarm.
370MBX
Open the battery drawer, insert the battery
contacts first according to the markings on the inside of the drawer front, close the drawer
and test the alarm using the test button before turning on the mains electricity supply.
Fit either locking key into the ‘Key Slot
above the battery drawer handle. Key number 1 locks
the alarm to the base, key number 2 locks the alarm to the baseplate AND the battery drawer
closed. These keys remain in place and should only be removed when opening the battery
drawer or removing the alarm from the baseplate.
LOCKING PINS / KEYS MUST BE FITTED. DO NOT ATTEMPT TO REMOVE THE ALARM FROM
THE BASEPLATE WITHOUT FIRST REMOVING THEM.
10. Switch on the mains electricity supply.
11. Check that the green light is on and that the red light is flashing every 45 seconds or so.
The lights are located behind the grille on the front of the alarm.
12. Press and hold the test button until the alarm sounds. NOTE: On the 670 series, pressing this
button places the alarm in pause mode.
SYSTEMS OF MORE THAN ONE ALARM
Test each alarm in the system checking that all other alarms in the system are triggered within 10
seconds.
WARNING
Do not attempt to test the alarm with flame heat or smoke, the results may be misleading and
may damage the alarm.
The dust cover must be removed as late as possible before commissioning. This will reduce the
chances of the alarm being contaminated by building dust etc.
Remove the alarm from the system before testing the wiring with high voltage insulation testing
equipment otherwise this will damage the alarm and will invalidate the warranty.
C: WHERE TO LOCATE
1. As a minimum smoke alarms should be located between sleeping areas and potential sources
of fire such as living rooms and kitchens. In single storey homes with one sleeping area a
smoke alarm should be installed in the hallway as close as possible to the living
accommodation. To ensure audibility in the bedrooms it may be necessary to install more than
one smoke alarm, particularly if the hallway is more than 15m long. In single storey homes
with two separate sleeping areas, a minimum of two smoke alarms is required, one outside
each sleeping area. In multilevel or split level homes as a minimum a smoke alarm should be
installed on the ground floor between the staircase and any rooms in which a fire might start
and on each storey in circulation areas which form part of the escape route (normally hallways
and landings).
NOTE: Heat alarms should not be used in escape routes instead of smoke alarms. They should
only be used in the applications listed below in addition to smoke alarms and should always be
interconnected to smoke alarms.
2. Additional alarms should be installed in bedrooms in anticipation of fires originating there,
caused by faulty wiring, lights, appliances, smokers or other hazards.
OWNERS
MANUAL
For further information
please write:
Dicon Safety Products (Europe) Ltd.
P.O. Box 402
GLOUCESTER
GL2 9YB
COVERS Simple Fitting Instructions • Location Guide
• User Information • Basic Fire Safety Tips
• Simple Maintenance Instructions
IMPORTANT: PLEASE READ
AND RETAIN THIS OWNERS MANUAL
MAINS POWERED
When installing this alarm for use by others, please
leave this manual or a copy with the end user.
MODELS:
PHOTOELECTRIC SMOKE ALARMS
650M, 650MC, 650MRB 650MRL, 650MBX
IONIZATION SMOKE ALARMS
670M, 670MC, 670MRB, 670MRL,
670MBX, 370MBX
HEAT ALARMS
680M, 680MC, 680MRL, 680MRB, 680MBX
220-240VAC ( )
MAINS POWERED ALARMS
CLASS II APPARATUS
2502-A0033
EARTH
BLACK or GREY (INTERLINK)
BLUE (NEUTRAL)
BROWN (LIVE)
WHITE
BROWN
BLUE
BASEPLATE
INSTALLATION USING JUNCTION BOX
ALARM
JUNCTION BOX
BATTERY
ACCESS
DOOR
Diagram 1
WHITE
BROWN
BLUE
BASEPLATE
ALARM
EARTH
BLACK or GREY (INTERLINK)
BLUE (NEUTRAL)
BROWN (LIVE)
PATTRESS
BATTERY
ACCESS
DOOR
Diagram 2
Question and Answer IconNeed help?

Do you have a question about the Dicon 650M and is the answer not in the manual?

Summary

MAINS POWERED SMOKE ALARMS & HEAT ALARMS

GUIDANCE ON INSTALLATION

Essential guidance for electrical installation, circuit requirements, and interconnecting alarms according to standards.

INSTALLATION

Step-by-step instructions for wiring, including new cable colour coding and connection methods.

WHERE TO LOCATE

Location Guidelines

Recommendations for optimal placement of smoke and heat alarms and areas to avoid for effective detection.

USER INFORMATION

Details on alarm features, operating lights, pause function, and essential fire safety advice for users.

SIMPLE MAINTENANCE, BATTERY REPLACEMENT & TROUBLESHOOTING

Simple Maintenance

Instructions for regular cleaning and testing of alarms to ensure optimal performance.

Battery Replacement

Procedures for changing batteries in various MBX and other model types.

Troubleshooting and False Alarms

Guidance on identifying and resolving common alarm issues and managing false alarms.

IMPORTANT NOTES, DISPOSAL & GUARANTEE

Radioactive Content and Disposal

Information regarding the radioactive content of ionization alarms and proper disposal methods.

Guarantee

Details on the product warranty and conditions for service.

Overview

This document describes a range of Dicon Mains Powered Smoke and Heat Alarms, including Photoelectric Smoke Alarms (650M, 650MC, 650MRB, 650MRL, 650MBX), Ionization Smoke Alarms (670M, 670MC, 670MRB, 670MRL, 670MBX, 370MBX), and Heat Alarms (680M, 680MC, 680MRL, 680MRB, 680MBX). These are 220-240VAC Class II apparatus designed for mains power. The manual emphasizes the importance of reading and retaining the owner's manual, especially when installing the alarm for others, in which case a copy should be left with the end user.

Before initial use, specific checks are required. For 370MBX, 650MBX, 670MBX, and 680MBX models, users must ensure the battery is fitted correctly and that the alarm is not beeping. A crucial step is to test the alarm before switching on the electricity supply. For all alarm types, users should verify that the green light (located behind the front grille) is on and that the red light flashes approximately every 45 seconds. When dealing with linked alarms, it's essential to check that all interconnected alarms activate within 10 seconds during a test.

The manual highlights several important notes regarding alarm behavior. The 370MBX model will beep for 10 minutes if its pause button has been pressed. Alarms equipped with rechargeable batteries or capacitor backup may beep for up to 2 hours while these components are charging. It is strongly advised to leave a copy of the handbook with the user and ensure they understand how to use and maintain the alarm.

Installation Guidance

Installation must be performed by a qualified electrician in accordance with BS7671. A permanent connection to the building's fixed wiring should be made in a suitable junction box. The alarm must be protected from dripping or splashing. To prevent contamination, especially in new builds, the alarm should be connected as late as possible in the installation process. The dust cover must be removed before applying power. Detailed guidance on alarm siting is provided in section C of the handbook.

A critical point is that the circuit powering the alarm must be a 24-hour voltage circuit that cannot be turned off by a switch. BS5839 Part 6 specifies that for mains-powered alarms with an integral standby supply (Grade D), the mains electricity supply should either be an independent circuit at the dwelling's main circuit board (with no other electrical equipment connected, except a dedicated monitoring device for supply failure) or a separately electrically protected, regularly used local lighting circuit. For mains-powered alarms without standby supply (Grade E), only an independent circuit as described above is permissible. If an RCD is used for protection, it must operate independently of any RCD protection for circuits supplying sockets or portable equipment. All interconnected alarms must be installed on a single final circuit.

The maximum interconnect wiring length is 250 meters, and a maximum of 12 alarms can be interconnected. Dicon smoke alarms should not be connected to models from other manufacturers. Alarm locations must comply with applicable building codes and the advice in section C.

Installation Procedure

The manual provides important information regarding electrical cable colour coding changes. Old colours (Red, Yellow, Blue, Black) correspond to new harmonized colours (Brown, Black, Grey, Blue) for L1, L2, L3, and Neutral, respectively. These new colours have been in use since March 31, 2004, and became mandatory after March 31, 2006. When selecting cable for interlinked smoke alarms, the interlink wire should be treated as live.

Two installation methods are illustrated: one suitable for plasterboard ceilings with void access and a junction box, and another for concrete or similar ceilings where access is insufficient or surface wiring is necessary. Users must connect the brown wire to the brown (live) in the house wiring and the blue wire to the blue (neutral). No connection should be made to the mains electricity supply earth terminal; instead, the house wiring earth should be terminated in a spare connector.

For multiple alarm installations, a "three core and earth" style cable should be used between all interconnected alarms. The third core of this cable connects to the white wire from the smoke alarm. The earth wire must not be used for the interconnect line; it must be treated as live, meaning it should be insulated and sheathed. If an alarm is not to be interconnected, the unused wires should be capped. The baseplate is removed from the alarm by twisting it anti-clockwise about 12mm, and the locking pin is detached.

Siting Locations

For optimal protection, smoke alarms should be installed in every room, excluding those listed in the 'Locations to Avoid' section. Heat alarms are recommended for kitchens, boiler rooms, laundry rooms, garages, and similar areas where smoke alarms would be unsuitable. All alarms must be interconnected.

In circulation areas, smoke alarms should be no more than 7.5m from the farthest wall, from any room door where a fire might start, from the next smoke alarm, and no more than 3m from a bed. When heat alarms are installed in a room, they should be no more than 5.3m from the farthest wall, from any room door where a fire might start, and from the next heat or smoke alarm.

The ideal location for an alarm, given the unpredictability of fire sources, is the center of a room or hallway. If wall-mounted, the detection element should be 150mm to 300mm (6 to 12 inches) below the ceiling, with the bottom of the alarm above doors and other openings. Heat alarms should not be wall-mounted. In rooms with sloped, peaked, or gabled ceilings, smoke alarms should be installed 900mm (3 feet) from the highest point to avoid "dead air" that could delay smoke detection. Closed doors and other obstructions can impede smoke and heat, so sufficient alarms should be installed to compensate. Local fire brigades or insurance companies can offer further advice, as can BS5839 Part 6 and guidance from the Department of Transport, Local Government and the Regions (DTLR). Research indicates that additional alarms significantly increase warning time, so following these guidelines for maximum protection is strongly recommended.

The manual provides diagrams for recommended alarm placement in single-storey (one and two sleeping areas) and two-storey dwellings, indicating smoke alarms for limited protection, additional smoke alarms for better coverage, and heat alarms. These alarms are primarily for single-family occupancy private dwellings; for other applications, manufacturer advice should be sought.

Locations to Avoid

Alarms should not be located in areas with turbulent air from fans, heaters, doors, or windows. High humidity areas like bathrooms or shower rooms, or where temperatures exceed 39°C (100°F) or fall below 5°C (40°F), should be avoided. The peak of an 'A' frame ceiling can accumulate "dead air" that prevents early detection. Alarms should not be less than 300mm (12 inches) from a wall when ceiling-mounted. Insect-infested areas can affect performance. Poorly ventilated kitchens or garages (for smoke alarms) can trigger nuisance alarms due to combustion particles from cooking or car exhaust. Very dusty or dirty areas can impair performance. Alarms should not be within 300mm (12 inches) of a light fitting or room corners. Locations that make routine testing or maintenance hazardous (e.g., over a stairwell) should be avoided. Poorly insulated walls or ceilings, and near objects like ceiling decorations that impede smoke or heat, are also unsuitable. Alarms should not be within 1500mm (5 feet) of a fluorescent light fitting, and wiring should be at least 1000mm (39 inches) away from these fittings. Alarms should not be installed on circuits containing fluorescent light fittings or dimmer switches.

User Information

Features:

  • Operating Lights: A continuous green light indicates mains power. A red light serves as an alarm source indicator and flashes approximately every 45 seconds to confirm circuitry integrity.
  • Alarm Source Indicator: The red light will flash every second in the unit that originated the alarm. Red lights on other interconnected alarms will flash every 45 seconds.
  • Alarm Pause (670 range only): This feature allows users to silence nuisance alarms (e.g., from cooking fumes) by momentarily pressing the test button. The red light will flash every ten seconds to indicate that the alarm is silenced. A double beep signifies that the alarm has automatically reset after approximately 10 minutes.
  • 370MBX Specific Pause: The 370MBX has a separate alarm pause button and will beep every 45 seconds for 10 minutes when in pause mode.

Be Prepared:

Smoke and heat alarms, when properly installed and maintained, are crucial components of a home fire safety program. Users should review fire hazards and eliminate dangerous conditions where possible. A well-prepared and practiced escape plan is vital in case of fire. Local fire brigades can provide advice. Users should familiarize themselves with the alarm signal, test doors for warmth before opening them (if warm, find another escape route), and prioritize evacuating all occupants over collecting possessions. The mantra is "GET OUT, STAY OUT, GET THE FIRE BRIGADE OUT!" After escaping, everyone should meet at a designated meeting place. If trapped inside, stay close to the floor, cover your mouth with cloth, and conserve breath while crawling to safety. All windows and doors should remain closed except for escape purposes. Users should prepare and practice an escape plan, including drawing a floor plan and conducting regular fire drills.

Simple Maintenance:

To ensure efficient operation, the unit should be vacuumed every six months. First, turn off the mains electricity supply. Use a soft brush attachment to vacuum through the vents, ensuring the nozzle does not touch the unit. Remember to switch the power back on after cleaning.

Testing the Alarm:

Test the alarm once a week by checking that the green light is on and the red light flashes approximately every 45 seconds (lights are behind the front grille). Then, press and hold the test button until the alarm sounds. Note that pressing the test button on 670 series alarms also activates the pause mode.

MBX Models - Battery Replacement:

For MBX models, the battery should be changed when the alarm beeps every 45 seconds.

  • 370MBX Models Only: Turn off the mains electricity supply. Remove the locking pin by inserting a small screwdriver into the square hole at the top of the battery drawer, applying pressure to push the pin up. The pin will pop out. Open the battery drawer, remove the old battery, and insert the new battery (contacts first, according to markings). Close the drawer and test the alarm using the test button. Refit the locking pin and then turn on the mains electricity supply. Note that the battery drawer cannot be closed if the battery is missing.

  • All other MBX Models (Excluding 10-year Lithium versions): Turn off the mains electricity supply. Remove the locking key, rotate the alarm approximately 10mm anti-clockwise, and remove the alarm from the ceiling. Unplug the alarm from the mains supply. Remove the screw and prise open the battery compartment door on the back of the alarm. Replace the battery with one of the following: Duracell MN1604, MX1604, Eveready PP3B PP3S, 6LF22 Gold Peak 1604A, 1604S. Close the battery door, refit the screw, and re-assemble the alarm to the ceiling, ensuring the mains plug is securely fitted. Test the alarm using the test button, then turn on the mains electricity supply. Note that the alarm cannot be fitted to the baseplate without a battery installed.

  • 650MBX-10, 670MBX-10, and 680MBX-10: These alarms are fitted with a 9-volt lithium battery. Replace with Ultralife U9VL batteries.

Troubleshooting:

The manual addresses common problems such as the alarm not sounding during a test, the green light being off, the red operating light not flashing, or the alarm emitting intermittent beeps. Suggested solutions include inspecting the wiring, gently vacuuming the alarm, and for MBX models, checking the battery. If these steps do not resolve the issue, users are advised to contact the manufacturer or a qualified electrician. If the alarm is still under guarantee, it should be returned to the distributor for repair.

False Alarms:

False alarms can be caused by abnormal air currents or dust. Users are warned not to disconnect the alarm if it is due to a false alarm, as this would disable its protective function. Dust can affect performance, and painting the alarm is discouraged. Other factors like cooking fumes or steam can also trigger false alarms.

Radioactive Content (Ionization type smoke alarms):

Ionization type smoke alarms contain a small amount of radioactive material (Americium 241, typically less than 37 kilobequerels). This represents no health hazard and is rigorously tested.

Disposal of Ionization Type Smoke Alarms:

As a responsible manufacturer, Dicon Safety Products adheres to all regulations and procedures regarding the disposal of ionization type smoke alarms, including changes in European legislation. For the latest information, users can contact Dicon Safety Products (Europe) Ltd.

Guarantee:

Dicon Alarms are guaranteed for 5 years from the date of purchase against faulty materials and workmanship under normal use. This guarantee does not cover damage from misuse or accidental damage. The guarantee is in addition to statutory rights. In the event of a problem, users should contact customer service.

Dicon 650M Specifications

General IconGeneral
Power Source9V Battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB
Operating Temperature40°F to 100°F (4°C to 38°C)
ComplianceUL 217

Related product manuals