DigiTOP
Acceptance certificate
The device has passed acceptance tests.
Batch number___________ Release date_____________
The correct operation of the device is guaranteed at ambient
temperatures from -25°C to +50°C and relative humidity from 30 to
80%.
To operate the device at subzero temperatures, it is necessary to
install it in a moisture-proof housing to avoid the formation of
condensation due to temperature changes.
Service life is 10 years.
8. Warranty
The warranty period for the device is 5 years from the date of sale.
During the warranty period, the manufacturer will repair the device
in the event of a malfunction, provided that the consumer has followed
the rules of storage, connection, and operation.
Warranty servicing of the device is carried out with the presence of
a marking from the selling organization.
The device is not eligible for warranty servicing in the following
cases:
1. Expiry of the warranty period.
2. Operating conditions and electrical connection do not comply
with the Operating manualprovided with the device.
3. User-performed self-repair.
4. The presence of signs of mechanical damage (violation of
seals, unauthorized appearance, scorching of power terminals from
the external side).
5. The presence of signs of exposure to moisture, foreign objects,
dust, dirt inside the device (including insects).
6. Lightning strike, fire, flooding, lack of ventilation, and other
causes beyond the manufacturer's control.
7. Storage, transportation and operation conditions
Devices in the manufacturer's packaging must be stored in
enclosed spaces with natural ventilation. Climatic factors of storage
conditions:
- air temperature: -50°С... +50°С;
- relative average annual humidity: 75% at +15°C.
The device is operational in any location in space.
The device is not intended for operation in conditions of vibration
and shocks, as well as in explosive environments.
Do not allow moisture to enter the input contacts of the terminal
clamps and internal elements of the device. It is prohibited to use it in
aggressive environments containing acids, alkalis, oils, etc. in the
atmosphere.
Dimensions
Wiring diagram
Input~230V
Load
IN
OUT
N
L
L` N`
90
35 67
3. Supply kit
- Voltage monitoring relay DigiTOP
- Operation manual
- Packaging
2. Technical specifications
Operating voltage, V 50-400
Operating frequency, Hz 45-65
Upper voltage threshold, V 210-270
Lower voltage threshold, V 120-200
Disconnect time at upper threshold, sec 0,02
Disconnect time at lower threshold,
sec, no more than 1(120-170V)
0,02(<120V)
Voltmeter accuracy, %, no more than 1
Power consumption, W, no more than VP-16/20/25/32A 2,5
VP-40/50/63A 1,5
Permissible pollution II
Electric shock protection class II
Degree of device protection IP20
The moment of tightening the screws of terminals, Nm 2,2±0,2
Operating temperature, °С -25... +50
Overall dimensions, mm 90x35x67
Voltage monitoring relay DigiTOP
series V-protector
16A, 20А, 25A, 32A, 40A, 50A, 63A
single-phase, digital
User-configurable parameters:
- (step 1V) 210-270V (250**)Upper voltage threshold
- (step 1V) 120-200V (170**)Lower voltage threshold
- (step 5 sec) 5-600 sec (15**)Switch-on delay time
- Indicator brightness level 1-9 (7**)
- Automatic button lock On/OFF (OFF**)
- Frequency control mode selection 50Hz/Auto (50Гц**)
- delay timeDisconnect
at upper threshold (“Auto” mode), ms 0-900 (200**)
*- under active load
4. Design and principle of operation
The device is controlled by a microcontroller, which analyzes the
mains voltage and displays the current effective value on a digital
display. The load is switched by an electromagnetic relay. The device
can work both with 50Hz household power grid and with voltage
sources with unstable frequency (generators, etc.). To do this, select
the appropriate operating mode in the settings menu.
The device disconnects the load if the voltage goes out of the set
range. The load is switched on automatically when the voltage returns
to the set range.
When the device is connected to the mains, the indicator will show
the current value of the mains voltage and will blink. Flashing of the
indicator means that there is no voltage at the device output. If the
mains voltage is within the set range (factory setting 170-250V), after
a switch-on delay (factory setting 15 sec) the load will be switched on
and the indicator will stop blinking. If the voltage is not in the set range
(less than 170V or more than 250V), the load will not be connected to
the mains until it returns to normal.
Allowable shutdown limits, switch-on delay time, frequency
control mode selection and digital display brightness level are set by
the user using the buttons located on the front panel of the device. All
set parameters are stored in non-volatile memory.
1. Purpose
The voltage relay DigiTOP of the V-protector series monitoring
(hereinafter referred to as the device) is designed to protect
consumers from overvoltage or undervoltage.
**- factory settings
Model
VP-16
VP-20
VP-25
VP-32
VP-40
VP-50
VP-63
Nominal current* I nom, A
16
20
25
32
40
50
63
Maximum current* I max, A
20
25
32
40
50
60
80
Nominal power*, kW
3,5
4,4
5,5
7,0
8,8
11,0
13,9
2
Max. wire cross section, mm
6
6
6
6
10
16
16
r.13_220421
Operating manual
Warranty and post-warranty service is provided by
DIGITOP ELECTRIC sp. z o.o. NIP: 6772469881
ul. Świętokrzyska 12/323 , 30-015 Kraków, Poland
Tel (+48) 794 267 868, e-mail: info@digitopelectric.pl