Activation
Level: 1.5”
1. Power system o.
2. Cut one wire going to the compressor contactor. (Step 2)
3. Connect Condensate Cop wires to the cut ends and install wire nuts. (Step 3)
4. Before mounting the Condensate Cop to the drain pan, test operation by
turning the Condensate Cop upside-down (inlet grill facing upward).
a. Power up system and set thermostat to call for cooling. Compressor should
not run.
b. Turn the Condensate Cop to the correct operating position. Float should
move to the bottom of the oat housing and the compressor should start.
CAUTION: Rapid cycling of the compressor must be avoided to prevent
overload. DO NOT SHAKE the Condensate Cop during the system test.
c. It is recommended that you test the Condensate Cop and drain pan with
water to prove water tightness and shutdown operation.
5. Attach the Condensate Cop to the secondary drain pan.
See illustrations. Hand tighten only.
6. Adjust sensor probe position to touch bottom of drain pan. Probe may be
adjusted to compensate for drain pans with angled sides.
Hand Tighten Only
Position Float
Probe Vertically
Thermostat Air Handler Condensate Cop
TYPICAL CONNECTION
3. Connect 2 wires
to cut ends
2. Cut
*For use with 24 VAC control circuits.
*Always test the system aer
installation of any new control to
ensure compatibility.
SPECIFICATIONS:
CURRENT CAPACITY:
Can operate contactor coils requiring up to
1.25 Amps.
POWER REQUIREMENTS:
Operates in series with 24 VAC contactor load.
ACTIVATION LEVEL:
1.5 inch depth from bottom of probe.
®
Condenser
Condensate Cop
Installation Instructions
MODEL NO. CC-1
Patent Pending
800.995.2222
®
www.diversitech.com
Installation:
Question and Answer IconNeed help?

Do you have a question about the DIVERSITECH Condensate Cop CC-1 and is the answer not in the manual?

DIVERSITECH Condensate Cop CC-1 Specifications

General IconGeneral
TypeCondensate Overflow Switch
Voltage24V AC
MaterialPlastic
ColorWhite
Switch TypeFloat
Operating Temperature32°F to 120°F

Summary

Installation Instructions

Power System Off

Ensure the power system is turned off before commencing installation.

Wire Connection to Contactor

Cut one wire to the compressor contactor and connect Condensate Cop wires.

Pre-Mounting Operation Test

Test unit operation by turning it upside down before final mounting.

Attach to Secondary Drain Pan

Mount the Condensate Cop to the secondary drain pan using hand-tightening.

Adjust Sensor Probe

Set the sensor probe to touch the drain pan bottom, adjusting for angled sides.

Specifications and Wiring

Current Capacity

Can operate contactor coils requiring up to 1.25 Amps.

Power Requirements

Operates in series with a 24 VAC contactor load.

Activation Level

1.5 inch depth from the bottom of the probe.

Typical Connection Diagram

Illustrates wiring connections for Thermostat, Air Handler, and Condensate Cop.