EasyManua.ls Logo

dIXEL XB570L - User Manual

dIXEL XB570L
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
dIXEL
Operating and Instructions Manual
1592006100
1592006100 XB570L GB r1.0 04.11.2004.doc XB570L 1/6
XB570L
BLAST CHILLER - QUICK CHILL AND HOLD FUNCTION
Contents
1. General warning_______________________________________ 1
2. General Features ______________________________________ 1
3. Mounting & Installation__________________________________ 1
4. Electrical Connections __________________________________ 1
5. Connections __________________________________________ 1
6. Frontal panel _________________________________________ 1
7. Front Panel Commands _________________________________ 2
8. How To Select A Cycle. _________________________________ 2
9. How To Start The Selected Cycle._________________________ 2
10. How to temporarily stop the running cycle. __________________ 2
11. How to definitively stop the cycle. _________________________ 2
12. How To Modify The Set Point Of The Hold Mode. _____________ 2
13. How to start a manual defrost. ____________________________ 2
14. How A Cycle Is Done. __________________________________ 2
15. Function And Parameter Programming Menu ________________ 3
16. Accessing “Pr2” and SECURITY CODE input ________________ 4
17. List of parameters______________________________________ 4
18. Printer management____________________________________ 5
19. IV configurable relay. ___________________________________ 5
20. Digital configurable input.________________________________ 5
21. ALARM SIGNALS _____________________________________ 5
22. Technical data ________________________________________ 6
23. Standard Value of the cycles._____________________________ 6
24. Standard Values of the parameters.________________________ 6
1. General warning
1.1
PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the
instrument for easy and quick reference.
The instrument shall not be used for purposes different from those
described hereunder. It cannot be used as a safety device.
Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the
operating limits avoiding sudden temperature changes with high
atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of
maintenance.
The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the
distributor or to “Dixell s.r.l.” (see address) with a detailed description of
the fault.
Consider the maximum current which can be applied to each relay (see
Technical Data).
Ensure that the wires for probes, loads and the power supply are separated
and far enough from each other, without crossing or intertwining.
Fit the probe where it is not accessible by the end user.
In case of applications in industrial environments, the use of mains filters
(our mod. FT1) in parallel with inductive loads could be useful.
2. General Features
The series XB has been created for fast chilling or freezing goods according
to international food safety standards.
There are FOUR types of cycles:
The CYCLES: Cy1, Cy2, Cy3, Cy4 are pre-set according to the most
common cycles used in food - safety applications; the user can select
one of them according to his own requirements and modify it as he
wants.
Any cycle can be manually terminated before the normal.
Any cycle can use the third probe like an “insert probe”, it measures the
internal temperature of the product.
During the Cycle there are no defrosts and the fans are always on, a
defrost cycle can be done before any freezing cycle.
The cycle is divided up to 3 phases completely configurable by the user.
Each instrument is provided with an output for remote display XR REP,
which shows the temperature of cabinets or goods.
The XB570L controller is provided with internal real time clock and can
be connected to the XB05PR printer. This means that a report, which
includes all the main features of cycle, can be printed: start and end of
the cycle, length of the cycle, logging of the temperature of the cabinet
and goods.
3. Mounting & Installation
Model XB570L is a controller panel mounted, hole dims 150x31 mm, and
fixed with the screws. The ambient working temperature range should be
between 0÷60°C. Avoid locations subject to heavy vibration, corrosive gases
or excessive dirt. The same applies to the probes. Ensure ventilation around
the instrument.
4. Electrical Connections
The instruments are provided with a screw terminal block to connect cables
with a cross section up to 2,5 mm
2
. Before connecting cables make sure the
power supply complies with the instrument’s requirements. Separate the
input connection cables from the power supply cables, from the outputs and
the power connections. Do not exceed the maximum current allowed on
each relay, in case of heavier loads use a suitable external relay.
4.1 PROBES CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due
to casual liquid infiltration. It is recommended to place the thermostat probe
away from air streams to correctly measure the average room temperature.
Place the defrost termination probe among the evaporator fins in the coldest
place, where most ice is formed, far from heaters and from the warmest
place during defrost, to prevent premature defrost termination.
5. Connections
Digital inp.
Evap.
Insert
Room
XB570L
Def.
Alarm/
AUX Fan
12A
250Vac
MAX
20A
8A
250Vac
8A
250Vac
Supply
230Vac
Comp
8A
250Vac
1913 14 15 16125678910111 2 3 4 17 18
6. Frontal panel
Aux
1 2
3 4
6.1 MEANING OF THE LEDS’
A series of light points on the front panels is used to monitor the loads
controlled by the instrument. Each LED function is described in the following
table.
LED MODE ACTION
ON - Compressor enabled
Flashing
- Programming Phase (flashing with LED )
- Anti-short cycle delay enabled
ON - Fans enabled
Flashing
- Programming Phase (flashing with LED )
- Activation delay active
ON - Defrost active
Flashing - Drip time active
ON - Freezing cycle or hold mode active
Flashing - Instrument temporarily stop
ON - Alarm signalling
- In “Pr2” indicates the parameter is also present
in “Pr1”
AUX ON - IV relay enabled
Question and Answer IconNeed help?

Do you have a question about the dIXEL XB570L and is the answer not in the manual?

Summary

General Warning

Safety Precautions

Check supply voltage, avoid water/moisture, disconnect before maintenance.

General Features

Mounting & Installation

Electrical Connections

Probes Connection

Mount probes with bulb upwards, avoid air streams for thermostat probe.

Front Panel

Meaning of the LEDs

Light points on the front panel monitor loads. Each LED function is described in the table.

Front Panel Commands

When a Cycle is Not Active

Controls for setting Hold Mode, manual defrost, and starting/stopping cycles.

Key Combinations

Specific key combinations for unlocking, entering menus, and navigating.

When a Cycle is Active

Controls for displaying set points, duration, and temporarily/manually stopping cycles.

How to Select a Cycle

How a Cycle Is Done

Configurable Cycle Parameters

Parameters like iS1, rS1, Pd1 for phases, and dbC, dbH, HdS for defrost and hold.

Function and Parameter Programming Menu

Function Menu

Includes all the main functions controlled by the instrument.

Access Procedure

Steps to access the function menu and navigate through parameters.

List of Functions

Details on functions like probe display, user parameters, installer parameters, and cycle management.

Accessing Pr2 and Security Code Input

List of Parameters

Regulation

Parameters for differential, anti-short cycle delay, and second compressor configuration.

Defrost

Parameters for defrost type, interval, termination temperature, and maximum length.

Fans

Parameters for fan operating mode, stop temperature, and delay after defrost.

Alarm

Parameters for maximum/minimum temperature alarms and alarm delay.

IV Configurable Relay

OAC=AL: for remote alarm

The IV relay is switched ON when an alarm happens.

OAC=Li: light

The light is switched on pressing the DOWN key or when the door is opened.

OAC=UL: UV light for a sterilisation cycle

Used for a sterilization cycle of the machine. Enabled when controller is not working.

Digital Configurable Input

Alarm Signals

Standard Values of the Cycles

Standard Values of the Parameters

dIXEL XB570L Specifications

General IconGeneral
BranddIXEL
ModelXB570L
CategoryChiller
LanguageEnglish