to the input CPOM of the TOC box.
The activation of this input will start PHASE 1 of the operation (also called evacuation) and will not allow elevator car
calls without the activation of the fire-fighters key-switch. Using these settings and once the contact has been
activated by the external fire contact, the elevator will go to the programmed floor, open the doors and remain
stopped (PHASE 1). The Landing Operation Panels are disabled and the Car operating Panel remains in operation
but only after turning on the fire-fighters key at the floor (input POM). The reactivation of the elevator will take place,
(bringing the elevator to the programmed floor), by turning off
the key and deactivating the contact from the external
fire contact.
Enter the menu “SPECIAL FUNCTIONS” submenu “FIREFIGHTERS” and set::
• The floor where the fire-fighters key is located
• The Access (if there are multiple doors)
• The stand-by state of the key switches and the external fire contact (NO or NC)
• The operation EN 81-72 (b)
• Connect the wiring as indicated in the electric diagram: the contact of the external unit must be connected together
with floor key switch POM (in serial for NC contacts, in parallel for NO contacts).
The activation of this input will start PHASE1 of the operation (also called evacuation) and will not allow elevator car
calls without the activation of the fire-fighters key-switch in the elevator car.
Using these settings and once the contact by the external fire contact OR the key at floor has been activated, the
elevator will go to the programmed floor, open the doors and remain stopped (PHASE 1). The Landing Operation
Panels are disabled and the Car Operating Panel remains in operation but only after the fire-fighter key in the CAR
(input CPOM) has been turned on. The reactivation of the elevator will take place, (bringing the elevator to the
programmed floor), by turning off
the fire-fighter keys (at the floor and in the elevator car) and deactivating the
contact from the external fire contact.