“Doors” Menu
----->>>>> ----->>>>>
OR
----->>>>> ----->>>>>
Floor 0 - 12:30:56
< Doors >
Parameter Description Navigation Values
Default
Value
- Floors: 2 <-
> 16 [32]
- Ofst 0 <->
N° floors
Flrs. : 2
Ofst : 0
Multiplex
Call
In multiplex installations a floor call can be
differentiated with a long push-button pressure
(more than 3 seconds) calling:
a) The installation with lower "Lift No (LN)"
parameter (for example if there is a duplex
installation with a big cabin for disabled
passengers and a smaller one, the greater must
be set as "1" and the other as "2";
b) In an “asymmetric floor distribution” system,
the installation that can reach the lowest/highest
level.
◄► (Choice)
No;
Yes
No
Table of Parameters:
Parameter Description Navigation Values
Default
Value
Ret. ramp
on
Time before activation of the retiring ramp
▲▼
(Increase/Decrease)
0,1 s <-> 9,9
s
0,1 s
Ret. ramp
off
Time before deactivation of the retiring ramp
▲▼
(Increase/Decrease)
0,1 s <-> 9,9
s
0,1 s
Lock fault
time
Time before the activation of the lock fault
▲▼
(Increase/Decrease)
2 s <-> 60 s 15 s
Door open
delay
Time before door opening – for automatic door
▲▼
(Increase/Decrease)
0,1 s <-> 9,9
s
0,5 s
Parking
time with
open door
Lift car parking time with open door (in sec.)
▲▼
(Increase/Decrease)
1 s <-> 30 s 7 s
Table of Parameters