1100DH High Power Wireless Receiver Installation Guide Digital Monitoring Products
5
Transmitter Supervision Time
For Listed installations, program the transmitter supervision time in panel zone programming as listed in the
following table. Refer to the XT30/XT50 Series Programming Guide (LT-0981) for complete wireless programming
information.
Compliance Standard Listed Accessories
Supervision
Time
UL 1023 Household Burglary Alarm System Units Accessory 1100R Repeater
1101/1102/1103/1106 Universal Transmitters
1127W/1127C PIR Motion Detector
1135 Siren
1142 Two-Button Hold-Up Transmitter
9060/9063 Keypads
60
UL 634 Connections and Switches for use with Burglar Alarm
Systems Accessory
1100R Repeater
1101/1102/1103/1106 Universal Transmitters
60
UL 639 Intrusion Detection Units Accessory 1100R Repeater
1127W/1127C PIR Motion Detector
60
UL 365 Police Station Connected Burglar Accessory 1100R Repeater
1103 Universal Transmitter
60
UL 609 Local Burglar Alarm Units and System Accessory 1100R Repeater
1103 Universal Transmitter
60
UL 1076 Proprietary Burglar Alarm Units Accessory 1100R Repeater
1103 Universal Transmitter
60
UL 1610 Central Station Burglar Alarm Units Accessory 1100R Repeater
1103 Universal Transmitter
1135 Siren
9060/9063 Keypads
60
UL 268 Smoke-Automatic Fire Detectors 1100R Repeater
1164 Wireless Synchronized Smoke Detector
3
UL 521 Heat Detectors for Fire Protective Signaling Systems 1100R Repeater
1183-135F/1183-135R Heat Detector
3
UL 985 Household Fire Warning System Accessory 1100R Repeater
1135 Siren
9060/9063 Keypads
240