DIGITAL MONITORING PRODUCTS | CellCom SERIES COMPLIANCE LISTING GUIDE 3
NEW YORK CITY (FDNY) SPECIFICATIONS
Introduction
The programming specifications contained in this section must be completed when installing the CellComSLCF or
CellComF‑LTE‑V and iCOMSLF for New York City (FDNY) fire alarm communicator installations for IP communication
applications. Refer to the FDNY Certificate of Approval #6238 for the complete conditions of approval.
Network and Cellular Communication, Primary and Secondary
When installed as a central station Internet (Network) communicator or slave transmitter, both primary and secondary
channels of communication shall be required and shall meet the conditions below. Network communication (iComSLF)
shall be used as the primary channel of communication to the Central Station and a Cellular Communicator
(CellComSLCF or CellComF‑LTE‑V) shall be used as the secondary channel of communication or in reverse order: Cellular
Communicator (CellComSLCF or CellComF‑LTE‑V) as the primary channel and Network connection (iComSLF) as the
secondary channel.
iComSLF Primary and CellComSLCF or CellComF-LTE-V Backup Programming
iComSLF PROGRAMMING CellComSLCF or CellComF-LTE-V PROGRAMMING
Comm Type = NET Comm Type = CELL
Checkin Min = 5 Checkin Min = 5
Failtime Min = 5 Failtime Min = 5
Test Rpt = Yes Test Rpt = Yes
Test Freq = 1 Dy Test Freq = 1 Dy
CellComSLCF or CellComF-LTE-V Primary and iComSLF Backup Programming
CellComSLCF or CellComF-LTE-V PROGRAMMING iComSLF PROGRAMMING
Comm Type = CELL Comm Type = NET
Checkin Min = 5 Checkin Min = 5
Failtime Min = 5 Failtime Min = 5
Test Rpt = Yes Test Rpt = Yes
Test Freq = 1 Dy Test Freq = 1 Dy
Wiring
All wiring must be in accordance with NEC, ANSI, and NFPA 70. All network cabling must be installed in accordance with
NFPA 70 for communication circuits.
Additional Requirements
Program and install the equipment to comply with NFPA basic fire requirements. Refer to the Universal Fire Alarm
Specifications and ANSI/UL 864 Specifications in this document.
Z-Wave
Note: ZWave functionality has not been evaluated by UL.

Other manuals for DMP Electronics CellCom LTE-V Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics CellCom LTE-V Series and is the answer not in the manual?

DMP Electronics CellCom LTE-V Series Specifications

General IconGeneral
BrandDMP Electronics
ModelCellCom LTE-V Series
CategoryCell Phone
LanguageEnglish

Related product manuals