CellComSLCF and CellComF-LTE-V Commercial Fire Communicator Installation
ANSI/UL 864
Fire Protective Signaling Systems using Internet/Intranet/Cell Networks
A Performance Based Technologies system as defined in UL 864 10th Edition may be configured as CELL Primary with
or without a backup path. The system may be configured as the following:
Path 1 Type CELL Primary with no Backup
PATH 1 PROGRAMMING
Comm Type = CELL Checkin Min = 58
Path Type = Primary Failtime Min = 60
Test Rpt = No
Checkin = Yes
Model 685-R Back Box Installation
For Commercial Fire applications using the CellComSLCF or the
CellComF‑LTE‑V and the included red plastic Model 685‑R Back Box,
mount the Back Box to the wall with the 1” #6 screws included with
the fire communicator. Mount the fire communicator to the back box
with the 1/2” #6 screws. See Figure 2. Locate the fire communicator
within 20 feet of the control panel and route all wire in conduit.
CellComSLCF and CellComF-LTE-V for FACP
Communication Fail Output
For Future Use
# 6 Screws Included
with Backbox
Figure 2: Model 685-R Back Box Installation
Figure 3: CellComSLCF and CellComF-LTE-V
Wiring Diagram for FACP
24VDC Applications:
For 24VDC applications using the fire communicator, connect a
keypad using a Model 330‑24 4‑wire programming harness with
in‑line resistor.
Output 1:
Output 1 must be programmed as a Comm Fail output in Output
Options.
Installation Length:
Must be installed in conduit from the fire panel to the 685‑R
conduit box and located within 20 feet.
FACP Zone Input:
Program FACP Zone Input to indicate a communication trouble
locally.
+DC G Z1 Z2 Z3 G Z4+ Z4- O1 O2 T R
RB
J8
S3
J9
RESET
LOAD
S1
S2
CellComF-LTE-V
{
{
Main Fire Alarm
Control Panel (FACP)
FACP Zone Input
FACP Zone Input
Connect to terminal with
lowest voltage
Use EOL specified
by FACP
12/24VDC Aux Output
Ground
Output 1
+DC G Z1 Z2 Z3 G Z4+ Z4- O1 O2 T R
CellComSLCF/
CellComF-LTE-V

Other manuals for DMP Electronics CellCom LTE-V Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics CellCom LTE-V Series and is the answer not in the manual?

DMP Electronics CellCom LTE-V Series Specifications

General IconGeneral
BrandDMP Electronics
ModelCellCom LTE-V Series
CategoryCell Phone
LanguageEnglish

Related product manuals