CELLCOM SERIES UNIVERSAL
COMMUNICATORS
Compliance Listing Guide
BEFORE YOU BEGIN
This guide provides compliance information for the CellCom Series Universal Alarm Communicator. The CellCom‑LTE
Series Universal Alarm Communicator provides a fully supervised alarm communication path for any burglary,
commercial fire, or residential fire control panel. DMP recommends that you read through the contents of this guide
before starting the installation process. It describes the functions along with available installation options. Information
contained in this guide allows you to learn the operation, functionality, and programming features of the communicator
to meet specific applications. This guide covers all the requirements for installing the CellComF‑LTE Universal Alarm
Communicators for Commercial Fire installations. This document applies to the following models:
CellCom‑LTE Cellular Communicator
CellComF‑LTE Cellular Communicator for Commercial Fire
PROGRAMMING REQUIREMENTS
System Programming Option Requirements
Notice to users, installers, authorities that have jurisdiction, and other involved parties: This product incorporates
field‑programmable software. In order for the product to comply with the requirements of a certificated installation,
certain programming features or options must be limited to specific values or not used at all as indicated below.
PROGRAM FEATURE OR OPTION STANDARD PERMITTED? POSSIBLE SETTINGS SETTINGS PERMITTED
System Reports, RESTORAL ANSI/UL 864 Y NO, YES, DISARM YES, DISARM
Communication, CHECKIN MINUTES ANSI/UL 864 Y 3‑250 3‑58
Output Options, COMM FAIL OUT ANSI/UL 864 Y 0, 1, 2 1, 2
Table 1: Compliance System Programming Options
APPLICATIONS
CID and 4-2 Dialer Connection
Directly connect the tip and ring from the control panel to the communicator. See Figure 1. This connection captures
Contact ID messages from any fire panel that are based on the SIA communication standard DC‑05‑1999.09‑DCS.
Messages are then formatted into a Serial 3 message and sent to a DMP Model SCS‑1R Receiver or SCS‑VR Receiver.
Note: Dialer Connection cannot be used when using Zone 4 Bell Connection. Do not connect telephone company
wires to the communicator. Remove any connected telephone company wires from the control panel.
Use 18-22 AWG
for Power Supply
connection
+DC-
G
R2
Z1
O1
R1
T2
T1
O2
+Z4-
Z3
+
Tip 2
Ring 2
12/24 VDC Aux. Output
+
-
Ground
Control Panel
The panel or separate power
supply must be listed for fire,
regulated, and power limited.
Telephone
Jack
Connector
BELL -
BELL +
Telephone
Jack
Connector
No Connection
(Zone Inputs Not
Evaluated By UL)
Wiring to FACP shall be connected within 20 ft in the same room and routed in conduit.
If FACP only has one phone line, connect to T2, R2
Z2
Ring 1
Tip1
Figure 1: Wiring Diagram for Tip and Ring Connection